background image

ABSORPTION

DISTANCE

SUPPLY DUCT

AIRFLOW

AS35 Steam Humidifier

Quick Start Guide

3

PITCH*

DUCT

DISPERSION

TUBE

TUBELETS

5" MINIMUM

* PITCH STEAM HOSE DOWN 

FROM DISPERSION TUBE 

TO HUMIDIFIER:

  2"/FT (15%) MINIMUM 

WHEN USING STEAM HOSE.

  1/4"/FT WHEN USING 

HARD PIPE.

STEAM HOSE OR PIPE. 

INSULATE PIPE WITH 

1" FIBERGLASS 

TO REDUCE 

STEAM LOSS.

90° LONG 

SWEEP OR TWO 

45° ELBOWS

90-2510

2

90-1521

Choose a location in a 

conditioned space

Place outside the grow room if possible. The capacity of the 
humidifier is reduced by the length of the steam hose or pipe due 
to condensation. The maximum recommended length of steam 
hose is 6 feet. Use hard pipe insulated with 1" thick insulation 
rated for 212°F or higher for lengths greater than 6 feet. If 6-foot 
steam hose does not reach from humidifier to dispersion tube, 
splice in 1" copper pipe using 3/4" x 1" reducing coupling.  
See Installation Manual for more details.

•  The steam tubelets must face up 

regardless of the airflow direction 
in the duct. The plate is labeled 
“UP” to indicate proper orientation. 

•  On horizontal duct runs, install the 

dispersion tube low in the duct.  
On vertical duct runs, center the 
tube on the duct.

NOTE:

 If the dispersion tube is mounted on insulated ductwork, 

make sure the insulation is not more than 2" thick at tube location.

1

Duct location and 

absorption distance

Absorption distance is the unobstructed straight line distance 
needed for steam to be fully absorbed. 

•  Determine absorption distance based on the lowest air 

velocity that the system will see (refer to table below).

•  Locate dispersion tube in a straight section of duct, far 

enough upstream of any obstructions or bends in the duct.

ABSORPTION DISTANCE

Tonnage 

per CFM

Recommended 

Absorption 

Distance

5 ton 

2000 CFM

12 inches

10 ton 

4000 CFM

6 inches

CENTER

CENTER

Install dispersion tube

1

Отзывы: