NOVUS AUTOMATION
38/85
o
By Keyboard
: If configured, the display will be activated whenever a key is pressed and will remain active for 1 minute (until a key is
pressed again). This setting will follow the configured contrast.
o
Never
: If configured, it will keep the display off.
•
Contrast
: Allows you to configure the display contrast level. There are eight levels of contrast. The lowest level simplifies viewing at the upper
and lower viewing angles and the higher-level simplifies viewing at the front viewing angle.
•
Update Interval
: Allows you to configure how often the display information will be updated.
o
Use log interval
: If configured, it will cause the display information to be updated at each log range.
o
Interval
: Allows you to set a display update range in seconds that is smaller than the log range. This way, the input channels will be read
and will update the display at this range. The minimum range is 1 second; the maximum range is 18 hours.
13.1.2.3
CLOCK
•
Date/Time
: Allows you to set the date/time used to set the device clock.
•
GMT
: Allows you to configure the GMT of the place where the device will be used (preferably during first use). By default,
LogBox Wi-Fi
is set
to GMT 0.
•
Date/Time Format
: Allows you to configure the clock format to 24 hours or AM/PM.
13.3.2
ANALOG CHANNELS PARAMETERS
NXperience
NXperience Mobile
Android
iOS
Figure 4 –
Analog Channel Screen
•
Tag:
Allows you to set a name, which will be used as channel identification during a download, for the digital channel. The field accepts up to
16 characters.
•
Input Type:
Allows you to configure the type of sensor to be used in each analog channel.
•
Unit:
Allows you to configure the unit for each analog channel. In the case of temperature sensors, it is possible to select the units °C or °F.
For other sensors, it is possible to describe the unit with up to eight characters.
•
Mode:
Allows you to configure the operation mode to use for each analog channel. If "Instant" mode is selected, the channel is read, and the
value will be logged at each log range. If "Average" mode is selected, the device will take 10 channel readings within the log range and at each
log range the average of these 10 readings will be logged.
•
Decimal Places:
Allows you to configure the number of decimal places of each analog channel. Temperature Sensors can be configured to
show up to one decimal place. Other sensor types can be configured to show up to two decimal places.
•
Lower Limit:
If the sensor configured for the channel is a temperature or internal diagnostic sensor, the lower limit will be filled by the software
with the sensor’s lower limit. If the sensor configured for the channel is of the linear sensor type (mV, V, or mA), it will be necessary to fill in the
desired value to represent the minimum value of the chosen sensor.
•
Upper Limit:
If the sensor configured for the channel is a temperature or internal diagnostic sensor, the upper limit will be filled by the software
with the sensor’s upper limit. If the sensor configured for the channel is of the linear sensor type (mV, V, or mA), it will be necessary to fill in the
desired value to represent the maximum value of the chosen sensor.
•
Offset:
Allows you to make small adjustments to the readings of each channel. The configured Offset will be added to all readings performed
on the configured channel.