NOVUS AUTOMATION
31/85
ADDRES
MNEMONIC
DESCRIPTION
INFORMATION
113
EXTERNAL_VOLTAGE_VALUE
External voltage value.
Unit in volts with two decimal
places.
114
EXTERNAL_VOLTAGE_VALUE_MIN
Minimum registered voltage of external
source voltage.
Unit in volts with two decimal
places.
115
EXTERNAL_VOLTAGE_VALUE_MAX
Maximum recorded value of external source
voltage.
Unit in volts with two decimal
places.
121
MQTT_LAST_UPDATE_YEAR
Year of last submission to the MQTT Broker.
122
MQTT_LAST_UPDATE_MONTH
Month of last submission to the MQTT
Broker.
123
MQTT_LAST_UPDATE_DAY
Day of last submission to the MQTT Broker.
124
MQTT_LAST_UPDATE_HOUR
Hour of last submission to the MQTT Broker.
125
MQTT_LAST_UPDATE_MINUTE
Minute of last submission to the MQTT
Broker.
126
MQTT_LAST_UPDATE_SECOND
Second of last submission to the MQTT
Broker.
136
WIFI_IRSS
Signal quality between the device and the
Wi-Fi Gateway.
Unit with signal in dB with two
decimal places.
137
WIFI_GATEWAY_COM_STATUS
Wi-Fi communication status.
0.
Disconnected Gateway
1.
Connected Gateway
2.
Gateway password error
3.
Gateway not found
4.
Error receiving IP via DHCP
5.
Authentication error
138
WIFI_MQTT_STATUS
Communication status with MQTT Broker.
0.
Disconnected Broker
1.
Connected Broker
2.
Error resolving DNS
3.
Error when posting a
message in Broker
4.
Error when subscribing to
topic
140
WIFI_IP_ADDR_0_1
Address of the device on the network
(Higher part).
XXX.XXX.000.000
141
WIFI_IP_ADDR_2_3
Address of the device on the network (Lower
part).
000.000.XXX.XXX
142
WIFI_MASK_ADDR_0_1
Network mask (Higher part).
XXX.XXX.000.000
143
WIFI_MASK_ADDR_2_3
Network mask (Lower part).
000.000.XXX.XXX
144
WIFI_GATEWAY_ADDR_0_1
Network Gateway address (Higher part).
XXX.XXX.000.000
145
WIFI_GATEWAY_ADDR_2_3
Network Gateway address (Lower part).
000.000.XXX.XXX
237
CHD_ACCUMULATED_VALUE_HIGH
Accumulator pulse count value (Higher part).
Without conversion.
238
CHD_ACCUMULATED_VALUE_LOW
Accumulator pulse count value (Lower part).
Without conversion.
239
CHD_ACCUMULATED_VALUE_FLOAT_HIGH Accumulator pulse count value in the user
unit (Float – higher part).
240
CHD_ACCUMULATED_VALUE_FLOAT_LOW Accumulator pulse count value in the user
unit (Float – lower part).
Table 9 –
Registers Table
Below is the table of registers supported by the WRITE HOLDING REGISTERS and WRITE MULTIPLE HOLDING REGISTERS commands:
ADDRESS
MNEMONIC
DESCRIPTION
INFORMATION
68
BUZZER_STATUS
Current buzzer status.
0.
Inactive buzzer
1.
Active buzzer
1044
SETTING_YEAR
Year setting in UTC (GMT 0).
1045
SETTING_MONTH
Month setting in UTC (GMT 0).
1046
SETTING_DAY
Day setting in UTC (GMT 0).
1047
SETTING_HOUR
Hour setting in UTC (GMT 0).
1048
SETTING_MINUTE
Minute setting in UTC (GMT 0).
1049
SETTING_SECOND
Second setting in UTC (GMT 0).
Table 10 –
Registers table that allows writing (1)