Analytic Systems VTC615R Скачать руководство пользователя страница 1

INSTALLATION & 

OPERATION MANUAL

VTC615R
ISOLATED 
DC/DC VOLTAGE CONVERTER

8128 River Way, Delta B.C. V4G 1K5  Canada  T. 604.946.9981  F. 604.946.9983  TF. 800.668.3884  (US/CANADA)

www.analyticsystems.com

An ISO9001 and AS9100 Registered Company 

Battery Chargers 

 Inverters 

 Power Supplies 

 Voltage Converters

Содержание VTC615R

Страница 1: ...D DC DC VOLTAGE CONVERTER 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage Converters ...

Страница 2: ...Copyright 2005 2014 Analytic Systems Ware 1993 Ltd ...

Страница 3: ...ttery acid to drip on converter when reading gravity or filling battery 7 O P CONNECTION PRECAUTIONS Connect and disconnect DC output connections only after setting the I P power switch to the off position Analytic Systems does not recommend the use of the VTC615 Series Voltage Converters in life support applications where failure or malfunction of this product can be reasonably expected to cause ...

Страница 4: ...it All rackmount units come standard with High quality digital output meters to allow monitoring of output current and output voltage An optional Battery Back up is also available Specifications Electrical Input Nominal ip 24 36 48 72 Actual Vdc 20 35 30 45 40 60 65 90 Input Amps max 39 5 27 1 20 3 12 6 Input Fuse ATC 3 x 15 2 x ATC 15 1 x 25 1 x 20 Noise on Input 50 mV Electrical Output Output No...

Страница 5: ... 87 600 hrs Isolation Input Case Input Output 1500VDC 500V 24V I P Output Case 500VDC 1500VDC 48V O P Mechanical Specification Depth 13 5 in 34 3 cm Width 19 0 in 48 3 cm Height 2u 3 5 in Material Marine Grade Aluminium Finish Black Anodize Fastenings All 18 8 Stainless Steel Weight 12 0 lb 5 5 kg Connections Four contact output terminals Warranty 3 years Safety Designed to meet CSA 22 2 107 1 UL4...

Страница 6: ...sent the terminals will measure as a short circuit Assuming the output isolation diodes are present connect one 4 foot piece of 14 AWG red wire to each positive output terminal Connect all the positive wires to a distribution bus or connect them together and then connect from the common point to the load using the correct gauge of wire for the total output capability of all the supplies running in...

Страница 7: ...ry small flat blade screwdriver to rotate the potentiometer Clockwise increases the output voltage and counter clockwise decreases it METERS The meter shows simultaneous voltage and current It features bright red LED readouts to permit easy monitoring from many feet or meters away Operation The dry contact output fail relay is accessed through the small 3 connection terminal block at the back of t...

Страница 8: ...e maximum level The input voltage is not high enough for unit to operate LOW INPUT Indicates that the input voltage is below normal because The input voltage is not in the correct range for proper operation of the unit OVERTEMP Indicates that the voltage converter is running too hot because Too much power is being drawn turn off or unplug some devices The voltage converter is located in a poorly v...

Страница 9: ...mp Components Conformal Dipping and RTV Compound Option w Wide Temperature Operation 40 to 55 C incl Option SM High Voltage Protection on the DC Input Side Option d Paralleling Diodes Option FI Forklift Modifications Option F Open Frame No chassis just heat sink bars not for all products Special Input There is no charge for nominal output voltages ie 12 0 24 0 48 0 but this must be noted at the ti...

Страница 10: ...10 ...

Страница 11: ...ing will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed or altered in any way b Our invoice is unpaid c The defect is the result of misuse neglect improper installation environmental conditions non autho rized repair alteration or accident 7 No refund of t...

Страница 12: ... Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage Converters ...