background image

INSTALLATION & 

OPERATION MANUAL

BCD1015 SERIES

Battery Charger 

8128 River Way, Delta B.C. V4G 1K5  Canada  T. 604.946.9981  F. 604.946.9983  TF. 800.668.3884  (US/CANADA)

www.analyticsystems.com

An ISO9001 and AS9100 Registered Company 

Battery Chargers 

 Inverters 

 Power Supplies 

 Voltage Converters

Содержание BCD1015 SERIES

Страница 1: ...RIES Battery Charger 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage Converters ...

Страница 2: ...Copyright 2005 2016 Analytic Systems Ware 1993 Ltd Revised May 19 2016 ...

Страница 3: ... P power switch to off position ALL BATTERY CHARGERS 1 WARNING RISK OF EXPLOSIVE GASES i WORKING IN VICINITY OF A LEAD ACID BATTERY IS DANGEROUS BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY OPERATION FOR THIS REASON IT IS OF UTMOST IMPORTANCE THAT EACH TIME BEFORE SERVICING EQUIPMENT IN THE VICINITY OF THE BATTERY YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY ii To reduce ri...

Страница 4: ... and recommended rates of charge xiii Add distilled water in each cell until battery acid reaches level specified by battery manufacturer This helps purge excessive gas from cells Do not overfill For a battery without cell caps carefully follow manufacturer s recharging instructions Analytic Systems does not recommend the use of the BCD1015 Series Battery Chargers in life support applications wher...

Страница 5: ...be added factory option to allow monitoring of charging current and charging voltage Specifications Input Voltages Nominal ip 24 48 72 Actual Vdc 20 35 40 60 65 90 Input Amps max 66 7 34 21 Input Fuse slow blow 3 x ATC25 2 x ATC20 1 x ATC25 Output Voltages Nominal op 12 24 32 48 Float Vdc 13 6 0 05 27 2 0 05 36 3 0 05 54 4 0 05 Absorption Voltage Vdc 14 4 28 8 38 4 57 6 Charging Amps 60 40 30 20 A...

Страница 6: ...Canada p 604 946 9981 f 604 946 9983 tf 800 668 3884 US Canada www analyticsystems com info analyticsystems com General Efficiency 80 maximum output Stages 2 or 3 Temp Range 25 to 40o C maximum output Isolation Input Output Input Case 1500 Vdc 500 Vdc 24 V In Output Case 500 VDC 1500Vdc 48 V Out Length 14 5 in 36 8 cm Width 9 9 in 25 1 cm Height 5 5 in 14 0 cm Clearance 1 Inch 2 5 cm all around Ma...

Страница 7: ...shown below in the left hand drawing OUTPUT 1 OUTPUT 1 OUTPUT 2 OUTPUT 2 BATTERY BANK 1 BATTERY BANK 1 BATTERY BANK 2 High quality digital meters can be added to the charger factory installed only Both outputs can be monitored for current and voltage Meters Installation MOUNTING Mount the unit in a DRY location Allow at least 4 inches of clearance around the heat sink fins for adequate cooling POW...

Страница 8: ...ging light will be on After a period of time which may be minutes to hours the batter ies will reach the float voltage at which time the charging light will go off and the charging current will reduce as necessary to maintain the batteries at that voltage You may check this voltage at the output terminals of the unit with a good digital voltmeter As shipped from the factory the unit is preset to 1...

Страница 9: ...ge charger is the fastest charger It charges the battery at a constant current until the battery voltage reaches a slightly elevated level The battery is maintained at this voltage while the charging current diminishes to a low value and then the battery is switched to the float voltage where it can be maintained indefinitely However the charger cannot differenti ate between a current going to a l...

Страница 10: ...exceeds the maximum output current rating causing the output voltage to drop to maintain the current at the maximum level The input voltage is not high enough for unit to operate LOW INPUT Indicates that the input voltage is below normal because The input voltage is not in the correct range for proper operation of the unit OVERHEAT Indicates that the Battery Charger is running too hot because Too ...

Страница 11: ...RE SENSORS Up to 2 battery temperature sensors can be connected to the charger to allow temperature compensation of the battery charging voltage 1 is supplied with the unit If only the 1 sensor is used it MUST be plugged into the BATT 1 connection on the side of the unit If no sensor is used the charger will default to standard output voltage For installation instructions of the temperature sensor...

Страница 12: ...12 Page intentionally left blank ...

Страница 13: ...ing will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed or altered in any way b Our invoice is unpaid c The defect is the result of misuse neglect improper installation environmental conditions non autho rized repair alteration or accident 7 No refund of t...

Страница 14: ...14 Page intentionally left blank ...

Страница 15: ...15 Page intentionally left blank ...

Страница 16: ... Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage Converters ...

Отзывы: