Installation Sheet
RDA-ENC6B and ENC12B
Dimmer Enclosures w/Breakers
The RDA-ENC6B (
FG606-13
) and RDA-ENC12B (
FG606-14
) enclosures
provide secure mounting for all AMX Lighting and PROlink controllers, and
lighting modules. The enclosures also contain circuit breakers.
These enclosures are CE, UL, and C-UL approved. They include circuit
breakers and terminals for multi-phase wiring. They also provide 18
knockouts for 1/2", 3/4", and 1" conduits.
Installation Instructions:
•
For indoor use only.
•
Mount on vertical surface only.
•
Maintain 12" (304.88 mm) minimum clearance above and below the
enclosure.
•
Route class 1 conductors through upper conduit knockouts.
•
Route class 2 conductors through lower conduit knockouts.
•
Use 75°C (167°F) copper conductors only.
•
Install filler plate #28-10500 (RDA-EFP) in all unused openings.
•
Install only UL approved modules (see the UL Number Cross
Reference to AMX Lighting ID table on page 2).
Enclosure Weights:
•
RDA-ENC6B: 16.5 lbs. (7.48 kg)
•
RDA-ENC12B: 17.5 lbs. (7.94 kg)
Dimensions between center lines (from FIG. 2):
RDA-ENC6B:
•
A to B = 16.0" (406.4 mm)
•
B to C = 22.88" (581.2 mm)
RDA-ENC12B:
•
A to B = 16.0" (406.4 mm)
•
B to C = 22.88" (581.2 mm)
Radia enclosures must be mounted on a vertical surface with a minimum of
12" (304.8 mm) clearance above and below the enclosure.
Specifications
•
Maximum input wire #1/0 AWG (50mm²)
•
Maximum line input is 140 A (per enclosure )
•
Torque input wire to 44 in-lbs. (5.0 N/m)
•
Wire stripping length: 0.67 inches (17 mm)
•
Input 1 feeds channels 1, 4, 7, and 10
•
Input 2a feeds channels 5 and 11
•
Input 2b feeds channels 2 and 8
•
Input 3 feeds channels 3, 6, 9, and 12
•
Breakers are UL 489 listed 10,000 AIC, 100% Switching Duty,
Hydraulic-Magnetic
The following section cross references the UL ID module numbers and
AMX Lighting module IDs.
The modules identified are the only ones that can be used in the RDA-
ENC6B and RDA-ENC12B enclosures.
FIG. 1
Top, front, bottom, and side views of the RDA-ENC6B and RDA-ENC12B enclosures
TOP VIEW
SIDE VIEW
RDA-ENC12B
RDA-ENC6B
24.0"
(610 mm)
24.0"
(610 mm)
18.0"
(457.2 mm)
0.75"
(19.05 mm)
6.0"
(152.4 mm)
Top, side, and bottom
views are the same for
both enclosures.
Sample RDK-ENC12B kit
shown with 2 RDC-PDC
RDA-ENC6B Configurations:
- ENC6B/120 20 A Breakers
- ENC6B/240 10 A Breakers
RDA-ENC12B Configurations:
- ENC12B/120 20 A Breakers
- ENC12B/240 10 A Breakers
RDK Configurations:
- RDK-ENC6B with 1 RDC-PDC
- RDK-ENC12B/240 2 RDC-PDC
BOTTOM VIEW
Note:
LINE INPUTS: 140 A MAX PER ENCLOSURE
Use 75° C copper conductors only.
Torque terminals to 44 in-lbs.
FIG. 2
Bracket configuration
A to B
B to C
Bottom slot
Top slot
Configuration for
right and left
mounting brackets
for all Radia
enclosures.
Maximum mounting
screw size: #12