Current feedback goes from AO1 of the drive to the PLC Analog input-1 should be 
adjusted so that Torque current detected by the PLC & drive becomes same. 

-

 

Basic:

 - Drive will give the analog output1 as 0 to 5 v for 0 to rated motor current. For 

e.g. motor rated current is 87 A for 45 KW. So at 87 A, drive will give 5 V analog output 
from AO1 terminal. 

-

 

Now, PLC will accept this 0 to 5 V in the analog input. PLC will read this 0 to 5 V as a 0 to 
512 count.  

 

So, if current is 43 A then Drive will give 2.5 V & PLC will read 255 count. 
 
  PLC current = analog input count  x  Motor rated current /  512 (para-23) 

                         43    =            255              x             87                 /  512 
 

-

 

To check the torque current of the drive See the parameter no. D02-5 from the keypad. 

-

 

Now open the System Menu screen from the HMI & go inside the SYSTEM menu. See 
the parameter no. 22, 23, 24. Parameter 24 shows the current, which should be equal to 
drive Torque current in D02-5. Enter the value 512 in parameter 23. Now run the drive & 
see the current. If the current is different than the parameter 24 then adjust drive 
parameter C14-0 & C14 – 3 by increasing / decreasing the value & check the current is 
approximate same or not. 

 

 
 
 
 

Содержание ADAPT System

Страница 1: ...75kW Start up Guide ADAPT System AMTECH NOTICE 1 Read this guide thoroughly before using the ADAPT System and store in a safe place for reference 2 Make sure that this manual is delivered to the final...

Страница 2: ...OBSERVED 1 DO NOT OPEN THE FRONT COVER WHILE THE POWER IS ON 2 ALWAYS GROUND THE UNIT CASE THE GROUNDING METHOD MUST COMPLY WITH THE LAWS OF THE COUNTRY WHERE THE UNIT IS BEING INSTALLED THE UNIT MAY...

Страница 3: ...uries or physical damage Note that some items described as CAUTION may lead to major problems depending on the situation In any case important information that must be observed is described A qualifie...

Страница 4: ...eck both keys for Panel HMI door Check whether any damage is there or not Refer the drawing check each item panel with Bill of material attached with drawing Mount the panel at sufficient height Take...

Страница 5: ...utput terminal to motor i e R Y and B Now switch off the MCB Switch ON the mains supply Switch ON the mains MCCB for 2 second OFF again to verify the supply to the drive If drive is started stopped he...

Страница 6: ...de Set the C 03 0 1 i e select PSI 1 for Forward run Set the C 13 0 11 i e Motor Torque current Analog output to the PLC for current feedback Auto Tuning Decouple the Motor from the load Put Drive in...

Страница 7: ...ent is 43 A then Drive will give 2 5 V PLC will read 255 count PLC current analog input count x Motor rated current 512 para 23 43 255 x 87 512 To check the torque current of the drive See the paramet...

Страница 8: ...3852 Oakcliff Industrial Court Doraville GA 30340 Phone 770 469 5240 Fax 678 894 4043 E mail info amtechdrives com URL www amtechdrives com Contact Us Rep Distributor Address...

Отзывы: