Amphenol Wilcoxon TN14 Скачать руководство пользователя страница 1

Troubleshooting accelerometer installations

Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing  

ensures data integrity and can identify most commonly occurring problems. 

The troubleshooting techniques presented are very simple and can be performed using most monitoring 

systems and data collectors or simple test equipment. Many installation and sensor problems can be 

detected by measuring the bias voltage of the sensor. The bias voltage will indicate faulty cable routes and 

failed sensors. Many online systems are capable of trending the sensor bias voltage. Other problems can be 

detected by analyzing the time waveform and FFT spectrum. 

Accelerometer operation and response

Most accelerometer faults can be diagnosed by measuring the bias voltage of the sensor amplifier. If the bias 

voltage is within correct limits the sensor is most likely operating properly. Most cabling faults can also be 

isolated by measuring the bias. After the bias is checked, the time waveform and FFT spectrum will verify fault 

diagnosis or proper operation.

AC coupling and the DC bias voltage

The sensor output is an AC signal proportional to the vibration applied. This AC signal is superimposed on a 

DC bias voltage, also referred to as Bias Output Voltage (BOV) or sometimes rest voltage. The DC component 

of the signal is generated by the 2 mA constant current diode in the power supply. This DC voltage needs to be 

blocked by a coupling capacitor in the measurement equipment, leaving the AC output signal. Most vibration 

data collectors, monitors, and sensor power units contain an internal blocking capacitor for AC coupling. If not 

included, a blocking capacitor must be field installed.

What is bias voltage?

The majority of accelerometers, PiezoVelocity Transducers (PVT®), and pressure sensors have a biased 

output. Biased outputs are characteristic of two-wire sensors used to measure dynamic AC signals. Vibration 

and pressure are examples of dynamic signals that vary with time. The external power supply provides a DC 

voltage to the accelerometer.  This power supply voltage is normally 18 to 30 volts DC. The accelerometer 

amplifier circuit design establishes this voltage (or “biases” the voltage) to a preset level. This BOV is normally 

12 VDC, although it may vary depending on the manufacturer and sensor design. The accelerometer’s 

specification sheet provides further information on the BOV. The BOV is determined by the amplifier design 

and is not adjustable.  

The BOV remains the same regardless of the input power to the accelerometer, as long as the input power is 

within the specified range. For example, if the BOV is 12 VDC and the input power is specified as 18 to 30 V, 

then the BOV will be 12 VDC if the input power is 18 VDC. If the input power is increased to 30 VDC, the BOV 

will remain at 12 VDC. The BOV is set by the interaction of the amplifier circuit in the accelerometer and the 

constant current from the stand-alone power supply or the analyzer or data collector.

8435 Progress Drive

Frederick, MD 21701

Tel: +1 (301) 330 8811

[email protected]

wilcoxon.com

buy.wilcoxon.com

Wilcoxon Sensing Technologies

Содержание Wilcoxon TN14

Страница 1: ...capacitor in the measurement equipment leaving the AC output signal Most vibration data collectors monitors and sensor power units contain an internal blocking capacitor for AC coupling If not includ...

Страница 2: ...a true analog representation of the vibration the sensor is attempting to measure Measuring the BOV The constant current diode CCD limits the current supplied to the sensor It provides a constant cur...

Страница 3: ...een integrated to velocity or displacement may also produce ski slopes for various reasons Cable routing faults can also be detected by analyzing the FFT Multiples of the line power frequency usually...

Страница 4: ...dustrial sensors typically contain protection devices to prevent these types of failures Figure 4 BOV trend of a sensor exposed to long term excessive temperatures Erratic bias and time waveform The b...

Страница 5: ...ply voltage and ensure that the bias voltage is centered between supply voltage and ground voltage However the bias voltage and power supply are rarely adjustable For ex ample if you are using an 18 v...

Страница 6: ...cally coupled signals Using shielded twisted pair cable will also help minimize any magnetically coupled noise into the signal cable For example if a power cable is 440 volts and the vibration signals...

Страница 7: ...am release air leak cavitation etc Repair steam leak dump Use less sensitive sensor Place rubber pad under sensor 10 0 14 0 V Stable Very high low frequency ski slope No high frequency signal Choppy D...

Отзывы: