The parameters of the group “Channels” (available data items for cyclical transmission):
7.2 Communication segment
Index Subindex
Name
Object type
Attribute
Data type
Description
2302
Number of detected magnets
Variable
rw
Unsigned8
Current number of magnets detected on the sensor
2303
PSU voltage
Variable
rw
Unsigned16
Current power supply in mV
6020
Position values for multi-sensor devices
Array
Current position value of up to 30 magnets
0
Number of entries
Variable
ro
Unsigned8
1…30
Position value for magnets 1…30
Variable
ro
Integer32
6030
Speed value
Array
Current velocity value of up to 30 magnets
0
Number of entries
Variable
ro
Unsigned8
1…30
Speed value for magnets 1…30
Variable
ro
Integer16
6300
CAM state register
Array
With the sensor you can configure a CAM switch. For each magnet there is
one CAM channel. Each CAM channel supports up to four CAM positions.
The parameter “CAM state register” defines the status bit of the CAM in a
CAM channel for up to 30 magnets
• Bit value 0: CAM inactive
• Bit value 1: CAM active
0
Number of entries
Variable
ro
Unsigned8
1…30
CAM state register for magnets 1…30
Variable
ro
Unsigned8
6400
Area state register
Array
This object contains the actual area status of the encoder position for up
to 30 magnets. If the position is out of range, a bit will be set in the related
position line
0
Number of entries
Variable
ro
Unsigned8
1…30
Area state register for magnets 1…30
Variable
ro
Unsigned8
6503
Alarms
Variable
rw
Unsigned16
This parameter includes different alarms:
• Bit 0: The number of magnets detected on the sensor differs from
the number of magnets configured in the engineering tool
(index 2201 subindex 0)
• Bit 12: Power supply out of range
• Bit 13: Device error
Note: To output alarms the operating parameter “commissioning
diagnostic control” (object 6000) must be activated.
6505
Warnings
Variable
rw
Unsigned16
Bit 12: Synchronization error: Sensor is not synchronized to the clock
of the control
Note: To output warnings the parameter “commisioning diagnostic
control” (object 6000) must be activated.
Table 1: Index 2302, 2303, 6020, 6030, 6300, 6400, 6503, 6505