Amphenol nrgSMART CTRL Скачать руководство пользователя страница 6

 

  

nrgSMART Integrated Controller 

Amphenol Network Solutions 

All rights reserved. 4.16.2021 151881 A0

 

509.926.6000 

— amphenol-ns.com

 

 

 

  Since the CTRL panel does not provide power through the nrgNET cable, 

legacy nrgSMART 

panels will not communicate if connected to a CTRL panel.

 

 

  New SENS Sensor panels 

can be

 connected to legacy nrgCONTROL-BT or nrgBDFB-XLW 

external controllers. Up to 30 panels 
 

 

  When connecting new SENS Sensor panels to legacy controllers, the nrgCONTROL-BT and 

nrgBDFB-XLW external controllers 

still requires the use of a service link

 (p/n 400819) installed 

on the legacy controller.  

 
For flexibility, a Sensor panel can be upgraded to include an integrated Controller, and a CTRL panel can be 
downgraded to a SENS panel. Changes can be made in the field by exchanging a circuit board and front 
cover. See Section 2.4 for part numbers, and contact Amphenol Network Solutions for more details. 

1.3 Specifications 

Inputs:  

Specifications: 

Voltage range (nominal voltage) 

±12VDC, ±24VDC and ±48VDC 

Alarms:  

Specifications:  

Alarm relay contacts 

2A @ 30 VDC; 0.6A @ 60 VDC 

Max. alarm card power rating 

@12V: 18mA (0.22W) @24V: 20mA (0.48W); @48V: 30mA (1.44W) 

Alarm wire size 

#24 AWG, typical (#26 to #20 AWG) 

Terminals  

Wire wrap or mates with TE Connectivity 3-640428-3 

Compliance: 

Specifications: 

UL

 

Listed

 

NEBS

 

Level 3

 

Voltage Sensor (nrgSMART model only):

 

Specifications:

 

Sensor accuracy 

-19.99 to +19.99V: ± 0.3V  
-20V to -60V: ± 0.1V  
+20V to +60V: ± 0.1V 

Voltage measurement range 

-60 to +60 VDC 

NOTE:  
• Voltage measurement may be slightly different than at input terminal blocks due to the voltage drop within the panel.  
• Sensors are factory calibrated and do not require user adjustment. 

Current Sensor (nrgSMART model only):

 

Specifications:

 

Precision / accuracy 
 

±5% precision, ±0.25A accuracy 
Example: 40A current, will measure 40A ± (40A*5%) ± 0.25A  
= 40A ± 2.0A ± 0.25A 
= 37.75A to 42.25A 

Communication (nrgSMART model only):

 

Specifications:

 

nrgOS minimum required version 

nrgOS 4.1.0 

nrgNET communication protocol 

Proprietary serial protocol used to communicate between panels and 
controller 

nrgNET connector 

Removable 5-pin connector with screw down terminals, required only when 
connecting SENS panels to a controller (CTRL, nrgCONTROL-BT, or 
nrgBDFB-XLW) 

nrgNET connector functions 

nrgNET IN from a controller (CTRL, nrgCONTROL-BT, or nrgBDFB-XLW) 
or upstream nrgSMART SENS panel, nrgNET OUT to downstream 
nrgSMART SENS panel 

Содержание nrgSMART CTRL

Страница 1: ...nrgSMART Integrated Controller CTRL SENS versions System Configuration Guide...

Страница 2: ...he data and communications markets We design manufacture and distribute products for customers who need an end to end solution for network connectivity fiber power distribution and rack management We...

Страница 3: ...ensor Panel designation 5 1 2 3 Legacy nrgSMART Compatibility 5 1 3 Specifications 6 Section Two Operation 7 2 1 Operation Guidelines 7 2 1 1 nrgSMART Connectivity CTRL Versions 7 2 3 Parts Accessorie...

Страница 4: ...umes no liability from the application or use of these products Amphenol Network Solutions does not convey a license under its patent rights nor the patent rights of others This document and the produ...

Страница 5: ...be a nrgSMART panel with an integrated controller CTRL or to a legacy nrgCONTROL BT external controller or to a nrgBDFB XLW 1 2 3 Legacy nrgSMART Compatibility The new nrgSMART architecture differs fr...

Страница 6: ...d power rating 12V 18mA 0 22W 24V 20mA 0 48W 48V 30mA 1 44W Alarm wire size 24 AWG typical 26 to 20 AWG Terminals Wire wrap or mates with TE Connectivity 3 640428 3 Compliance Specifications UL Listed...

Страница 7: ...are release See Figure 1 Figure 1 CTRL Panel Connectivity Ports 2 The integrated nrgSMART Controller is set to DHCP client by default Connect an ethernet cable from the network to the LAN port on fron...

Страница 8: ...being monitored by the controller o Integrated Controller Name o nrgOS version o Number of active panels o IP address o Integrated Panel name o Integrated Panel serial number o Feed Current A and B o...

Страница 9: ...Interface 5 The nrgNET serial connectors nrgTEMP connectors and dry contact alarm terminals are located in the rear center of the panel Refer to Figure 2 Figure 2 Rear Connections nrg240GT54 panel sho...

Страница 10: ...eable Controller Card nrgSMART 400822 Replaceable Sensor Card nrgSMART 307607 Faceplate for Sensor Card nrgSMART 150158S E2 Faceplate for Controller Card nrgSMART 150619S E2 SENS to CTRL conversion co...

Страница 11: ...2 ICES 003 Class A Notice Avis NMB 003 Class A This Class A digital apparatus complies with Canadian ICES 003 Cet appareil num rique de la classe A est conforme la norme NMB 003 du Canada ELECTROSTATI...