2.2.6 Input Wiring
WARNING! Before connecting input power cables, make sure input power to the panel is turned off.
13.
Make sure input power is off before connecting the panel’s input cables to the PDU or battery.
14. For input wiring, crimp dual-hole compression lugs onto 2/0 AWG to 350 MCM copper wires. The choice of
input wiring depends on the following criteria:
•
Input interrupt device rating affects the size of input wiring.
•
Ambient operating temperature affects the type of input wire insulation. For further information,
consult the National Electrical Code (NEC).
15. Insulate the lug barrels with UL94 V-0 rated heat-shrink tubing.
16. Clean terminals and lugs with a non-abrasive, non-metallic pad.
17. If required, lightly coat antioxidant on lugs and input BATT and RTN terminals and then connect lugs to
input terminals, as shown in Fig. 2-6.
18.
Tighten nut to 150 in/lb. (~17 N•m), max.