The trip settings alter slightly for the Residual Voltage Protection Element version. In this version, the
existing trip time and level (although extended in available values) settings are utilised for the series
earth continuity resistance only. The shunt trip time setting becomes the Pilot Interlock Trip Time Setting.
The Pilot Interlock Trip Time setting is
also used for open circuit trip conditions (>100Ω). This means that
the EC settings that have a set trip point (shunt and open circuit faults) can have a separate trip time that
is significantly faster than the series EC setting, which is more commonly used for touch potential
protection.
7.3.1 Pilot Series
Table 8 Protection Element - Earth Continuity Series Trip Characteristics
Parameter
Action
Power Cycle
Trip status maintained
Reset
Requires a general reset after the trip condition has cleared.
Alternatively the trip can be automatically reset depending on the
status of the EC Latch parameter.
Trip Actions
Open Main Contactor Relay
Prevent Main Contactor from closing
Active Period
Always active
Logging
Logged only if outlet is running
Parameters
Trip time
Trip level
Trip latch enable
Monitoring
Available as the raw ohms measurement, resolution of 1
Ω.
7.3.2 Pilot Shunt
Table 9: Protection Element - Earth Continuity Shunt Trip Characteristics
Parameter
Action
Power Cycle
Trip status maintained
Reset
Requires a general reset after the trip condition has cleared.
Alternatively the trip can be automatically reset depending on the
status of the EC Latch parameter.
Trip Actions
Open Main Contactor Relay
Prevent Main Contactor from closing
Active Period
Always active
Logging
Always logged
Parameters
Trip time
Trip latch enable
Monitoring
Available as the raw ohms measurement, resolution of 100
Ω.