MPA3 V6.3 MOTOR PROTECTION RELAY MANUAL
Issue: R0, Date: 11/2010, CRN: 8168
MPAB010 Rev0
MPA3 V6.2 Motor Protection Relay Manual
Page 21
16
Adjustable Settings
The MPA settings can be reviewed and/or adjusted by selecting the 'MPA Settings Information' Page, Level 7. At
this level all the adjustable parameters are listed with their current value.
Although settings are available in both cases, the Modbus settings will not function on
a Motor Protection Relay if it is supplied with the Ethernet option, and the Ethernet
settings will not function if the relay is supplied with the Modbus option.
16.1
Common Settings
I(100%) =
Sets the basic current range
6xI Trip t:
Selects the overload trip time at six (6) times FLC
O/L Reset:
Selects the reset level as a % of the thermal accumulator
S-Cool Ratio: Allows the cooling rate of the thermal model to be modified
I Bal Trip:
Selects the current balance trip threshold as a % of FLC
SC I Trip:
Selects the short circuit trip level
SC Trip t:
Selects the trip time for the short circuit function
HI I Alarm:
Selects the high current alarm threshold as a % of FLC
O/Load Alm: Selects the overload alarm threshold as a % of the thermal accumulator
LO I Alarm:
Selects the low current alarm threshold as a % of FLC
EL:
Selects the sensitivity trip level for the earth leakage protection
EL Time:
Selects the trip time for the earth leakage protection
EL Alarm:
Selects the alarm trip level for the earth leakage protection
Ires Trp:
Selects the residual current trip threshold as a % of FLC
Ir Time:
Selects the trip time for the residual current function
ITst Mode:
Selects the insulation test mode or disables the function
ITst Trp:
Selects the insulation test trip threshold
ITst Alm:
Selects the insulation test alarm threshold
UV Level:
Selects the under voltage trip threshold as a % of line volts
RTD G1 T:
Selects the temperature trip threshold
RTD G1 A:
Selects the temperature alarm threshold
RTD G2 T:
Selects the temperature trip threshold
RTD G2 A:
Selects the temperature alarm threshold
An OP:
Selects the section to be monitored
16.2
Modbus Settings
Modbus:
Selects the communications baud rate
Modbus Ad:
Selects the Modbus Slave address