![Ampcontrol Gasguard GG2 DISPLAY Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/ampcontrol/gasguard-gg2-display/gasguard-gg2-display_user-manual_2934187054.webp)
Ampcontrol Pty Ltd
– ABN 28 000 915 542
GG2 DISPLAY USER MANUAL
GG2B023 Version 3
– JUNE/19
Uncontrolled Copy - Refer to Ampcontrol Website for Latest Version
Page 54 of 82
A
P
P
R
OV
E
D
FOR
E
X
T
E
R
N
A
L
D
IS
TR
IB
U
T
ION
–
P
R
OP
E
R
T
Y
OF
A
M
P
C
ON
TR
OL
P
T
Y
LTD
–
N
O
T
T
O
B
E
R
E
P
R
OD
U
C
E
D
I
N
P
A
R
T
Table 10: Modbus - Protocol Configuration - Settings
Field Name
Value
ADDRESS
Specifies the Modbus address for the system.
Validity: 1-247
PARITY
Specifies the parity setting for Modbus. Options: EVEN, NONE
or ODD
BAUD
Specifies the Baud Rate of the RS485 bus.
Options: 19200, 9600, 38400 or 115200
STOP BITS
Specifies the number of stop bits.
Options: 1 or 2
POWER MODE
Options: HIGH or LOW
*Power Mode can selected between 5V logic (HIGH) and 3.3V logic (LOW).
LOW power mode will sightly reduce current consumption and should only be connected to compatible
logic devices over short cables.
NOTE
LOW power mode should only be connected to compatible logic
devices over short cables
iMAC
6.4.4.1 Configuration
After selecting the iMAC protocol, it may be configured. Protocol configuration must be done via the
“PROTOCOL CONFIG” screen in the configuration menu. Within this menu, there are two screens,
ADDRESSES and GENERAL. For general guidance on editing options please refer to Section 6.1.2.2.
The ADDRESSES screen may be used to configure data addresses on the iMAC.
Table 11: iMAC - Protocol Configuration - Addresses
Field Name
Value
STATUS
Specifies the iMAC address for system status information.
Validity: 0-255.
ANALOGUE
Specifies the iMAC address for analogue (4-20mA output)
information. Validity: 0-255.
POWER SUPPLY
Specifies the iMAC address for system power supply
information. Validity: 0-255.
SYS CLOCK
Specifies the iMAC address for system clock information.
Validity: 0-255.
CAT RESET
Specifies the iMAC address for catalytic reset command.
Validity: 0-255.
BYPASS
Specifies the iMAC address for system bypass command.
Validity: 0-255.