FlameSAFE Water Fire Extinguisher Service and Maintenance

 

1

 

AMPAC Safety Pty Ltd does  not  service, maintain or recharge 

fire extinguishers. This service and maintenance information is a 

guide to assist qualified service personnel in the inspection and 

maintenance  of  AMPAC  Safety  FlameSAFE  fire  extinguishers 

only.  It  is  important  that  all  warnings  and  notes  on  the  fire 

extinguisher  and  in  AS1851  are  complied  with.  Serious  injury 

could occur if these instructions are not followed. AMPAC Safety 

assumes no liability for service, maintenance or recharge of fire 

extinguishers by publishing this document. 

When  maintenance  is  indicated,  it  should  be  performed  by 

trained persons using proper  equipment. Fire extinguishers are 

pressure vessels and must be treated with respect and handled 

with  care.  They  are  mechanical  devices  and  require  periodic 

maintenance to be sure that they are ready to operate properly 

and  safely.  Extinguishers  should  be  serviced  only  with  original 

and genuine spare parts 

– the use of substitute parts constitutes 

the void of any warranty covering the equipment. 

1. REGULAR INSPECTION

The  extinguisher  shall  be  inspected  in  accordance  with  the 

requirements of Australian Standard AS1851. 

2. EXTINGUISHER RECHARGE INSTRUCTIONS

Warning 

A. Before attempting to recharge be sure this extinguisher is

completely depressurized.

B. Use a regulated pressure source.

C. Check and calibrate regulator gauge at frequent intervals,

the regulator gauge should be used to determine when the

intended charging pressure has been reached, do not use

the extinguisher gauge for this purpose.

D. Never leave an extinguisher connected to a regulator of a

high  pressure  source  for  an  extended  period  of  time.  A

defective regulator could cause the cylinder to rupture due

to excessive pressure.

The  Fire  Extinguisher  is  to  be  recharged  in  accordance  with 

Australian Standard AS1851. 

Ensure the extinguisher is fully discharged by opening the

Discharge Valve until all pressure is released.

Remove the Discharge Valve from the cylinder.

Empty the remaining contents of the cylinder.

FlameSAFE Water 

Inspect  the  cylinder  internally,  with  the  aid  of  an

inspection light, to ensure cylinder is clean and free

from damage.

Inspect  the  cylinder  externally  to  ensure  it  is  free

from damage.

Fill cylinder with 9.0 litres of Water.

Check  Valve  Assembly  to  ensure  correct
operation. Lubricate Valve “O” Ring with petroleum
jelly.

Screw Valve Assembly into cylinder ensuring “O”
ring is correctly seated.

Pressurise  extinguisher  with  either  Air  or  Dry

Nitrogen to 700kPa.

Fix  Safety  Pin  to  handles  and  fit  Safety  Tie  to

prevent accidental discharge.

Examine extinguisher to  ensure that there  are no

leaks.