ADVANCED WARNING
SY ST EMS
LED Annunciator Master (LAM) NZS4512
Installation Guide
Item Numbers: 4310-0038
MAN2687-1
N1236
Page 1
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia
Tel: +61 8 9201 6100
Europe
Tel: +44 (0) 1302 833 522
New Zealand
Tel: +64 9 443 8072
www.ampac.net
Description:
The LAM and IP40 housing is supplied assembled and
ready to be mounted to any flat surface.
Features:
Remote alarm & fault / isolate zone indication (8 zones)
Remote FACP status indication
Lamp test and buzzer silence controls
ZoneSense PLUS Max 8 LAM’s per FACP (addresses
1-8)
Slip in label for Zone 1-8 or site specific information
(see LAB2656.DOC)
Programmed zones 1 (top) to 8 (bottom)
Installation:
Observe anti-static precautions at all times
1. Power down the FACP, disconnect the batteries
Release of the Clip On Surround: Push down
here, pull out and lift up to remove and insert label.
Lettering on slip in
label must be at
least 5mm in height.
Slip In Label
FIRE
DEFECT / ISOLATE
Windows for
Slip in Label
NOTE:
PCB
FIRE
DBA
DEFECT
NORMAL
SOUNDER DEFECT
ISOLATED
POWER
LAMP
TEST
SILENCE
BUZZER
FIRE
DEFECT / ISOLATE
Figure 1: Inserting Optional Site Label
2. Open the front door and remove the four (4) screws
securing the front cover to the housing.
3. Install an appropriate coupling into the housing
then mount using the three (3) knockout mounting
holes
4. See
Figures 1
and
2
if site specific label is to be
fitted
5. Set the address (1 to 8) on the LAM as in
Figure 2
6. See
Figure 3
for information on inserting the
termination link LK1 on the last card in the chain
7. Reassemble
8. Terminate the cabling from the FACP to the LAM
as shown in
Figure 3
9. Power up, connect the batteries and test
PWR OUT
PWR IN
+
0 V
+24V
COM
-
RS 485 OUT TO NEXT LAM
BUZZER MUTE INPUT
LINK
TERMINATOR
ADDRESS SWITCH
SET TO 1
LK1
CN6
ON
1
2
3
4
0V
+24V
+
COM
-
+ - SHLD
RS485
AUX
24VDC
RS 485 IN FROM FACP
PWR
OUT
PWR
IN
+
0 V
+24V
COM
-
RS 485 OUT TO
NEXT LAM
LINK
TERMINATOR
LK1
CN6
ON
1
2
3
4
0V
+24V
+
COM
-
RS 485 IN FROM
PREVIOUS LAM
+
0 V
+24V
COM
-
CN6
ON
1
2
3
4
0 V
+24V
+
COM
-
BUZZER MUTE INPUT
BUZZER MUTE INPUT
LAM 1
LAM 2
LAM 3
Field
Termination
in FACP
+ -
ADDRESS SWITCH
SET TO 2
ADDRESS SWITCH
SET TO 3
NOT USED - ONLY USED ON THE LAST LAM IN
THE CHAIN REMOVE AND STORE AS SHOWN
NOT USED - ONLY USED ON THE LAST LAM IN
THE CHAIN REMOVE AND STORE AS SHOWN
LINK
TERMINATOR
LK1
ONLY INSERTED ON THE LAST CARD
PWR
IN
RS 485 OUT TO
NEXT LAM
RS 485 IN FROM
PREVIOUS LAM
PWR
OUT
Figure 2: General Wiring of 3 LAM's