Description: 

The Primary Graphical User Interface (GUI) item number ‘

6350-GUIP’

 provides the Main Controls and Main 

LED block and the associated 5U mounting plate. The Primary GUI will always feature the user interface

 

in 

accordance with AS 4428.16 and AS 4428.4

 

It also provides the panel Menu structure via the Menu Button. 

EWCIE and EICIE  system  controls  and indications  can be  configured  according to your  installation 

requirements. There are optional ways to configure 

each

 GUI screen layout. 

 

Where more controls are required, additional secondary GUIs 

‘6350-GUIS’

 are added. 

The EvacU

Elite

 13U Cabinet supports a maximum of 3 GUIs (One Primary and 2 Secondary) The EvacU

Elite

 

24U Cabinet supports a maximum of 7 GUIs (One Primary and 6 Secondary). 
A Secondary GUI 

has less components than a Primary GUI

. E.g., there are no 

input terminals

 on the 

Secondary GUI. 

 

Connections:  

If  one  GUI  Board  is  connected  using a Cat 5 cable  between  the 

Primary

 

Rack DCPU  RJ45-1

  into the 

Primary GUI RJ45 -1.

 

When multiple GUI Boards are fitted, use Cat 5 cables to interconnect them (IN OUT daisy chain connection) 
Connect from the 

Primary Rack DCPU RJ45-1

 into the 

Primary GUI RJ45 -1

 then 

out on RJ45-2

 to the 

next 

GUI RJ45-1

 and

 out on RJ45-2

 until you connect the final GUI Board.  

Each GUI requires 

power connection on CN7. 

The power cable originates from the PSU and runs to CN7. 

When multiple GUIs are installed a daisy chain power cable connects’ In CN7 - Out CN6’ to the next GUI. 

Note:

  Where >3 GUIs are  installed  there is  a specific way to distribute the 27V  DC  power.  Refer to  the 

schematic drawing for further information. 

 
Considerations - Replacement of Faulty Boards  

If the 

Primary GUI

 Board failed and you need to replace the board it will be necessary to reload the system 

configuration BIN file software into the new GUI board and recycle the power afterwards.  
If the GUI failure involves a 

Secondary GUI

 board you need to set the “Address” on the GUI by pressing the 

CONFIG 

Button on the rear of the board then confirm the address setting from the touchscreen.       

Primary GUI Screen with LED Membrane Display Illustrated Below: 

 

8 EWS and 16 EIS control buttons shown configured on the Primary GUI above. 
The touchscreen is a 9-inch TFT LCD 800 x 480 with LED backlighting and resistive touch screen.  