Gas Release Panel Short Form Installation Guide 

Item Numbers: 2983-0304 

 

Connecting the Standby Batteries 

CAUTION: There is a risk of explosion if the battery is replaced by 
an incorrect type. Always dispose of used batteries in accordance 
with the battery manufacturers’ instructions.  
Note

: On a standard ‘as-supplied’ unit, PLK1 (‘Battery Monitoring’ link) is 

not fitted and a fault will occur on initial power-up if fully charged batteries 
are NOT connected. For the emergency standby power supply, only use 
good quality, sealed VRLA batteries. Position and connect the 2x12Vdc, 
7Ahr batteries, as shown in diagram (see right).

 

Connecting Circuits to the Main Control PCB

 

Terminate incoming and outgoing circuits at the Main Control PCB connectors (see Figure 2 overleaf).

 

Technical Specification 

POWER SUPPLY 

Mains Supply Voltage: 

230Vac, 50/60 Hz 

Internal Power Supply 

24Vdc Nominal 

Max. Output Current: 

3A@230Vac 

Power Rating (including charging): 

1.5A cont, 3A peak 

Battery Type: 

2 x 12Vdc, 7Ahr VRLA type, connected in series 

Battery charge Current: 

0.7A 

Earth Fault Monitoring:  

YES 

Mains supply/ Battery charger monitored for failure 

YES 

Quiescent Current drain on mains fail 

40mA 

DETECTOR CIRCUITS 

Number of Conventional detector circuits: 

3 @ 21-28Vdc 

Line Monitored for open and short circuit faults: 

YES 

Max. Cable length per circuit: 

250m 

Max. Number of smoke/heat detectors per circuit: 

20 

Max. Combined number of detectors and call points per circuit: 

32 

Zone quiescent current: 

2mA max. 

End-of-line resistor value: 

6K8 Ohm +/- 5%, 0.25W 

SOUNDER CIRCUITS 

Number of conventional sounder circuits: 

3 (two x 1

st

 stage, one x 2

nd

 stage) 

Line monitored for open and short circuits: 

YES 

Sounder output rating: 

21-28Vdc, fused @ 200mA per circuit 

Max. Sounder cable length per circuit: 

50m 

Max. Number of polarised sounders per circuit: 

10 @ 20mA each 

End-of-line resistor value: 

6K8 Ohm +/- 5%, 0.25W 

MONITORED INPUTS 

Number of monitored inputs: 

6 (Manual release, Flow switch, Low pressure, Mode, Hold, Abort) 

Thresholds: 

8K to 2K ohms (normal); 1.8K to 200 ohms (active); 150 to 0 ohms (short circuit) 

End-of-line resistor value: 

6K8 Ohm +/- 5%, 0.25W 

AUXILIARY OUTPUTS 

Number of auxiliary outputs*: 

6 (Fire, Local fire, Extract, 1st stage, 2nd stage, Fault) 

Extract time: 

Adjustable 1-900 seconds (1 second steps) 

Relay contact rating: 

30Vdc, 1A max. Note: DO NOT switch mains voltage using these outputs 

*Note; 5 Additional relay outputs (Reset, Mode, Discharged, Hold, Abort) are available on the GR Output Expansion Relay Board (Item No. 2980-0004) 

REMOTE INPUTS 

Number of remote inputs: 

4 (SIL, AL, FLT, RST) 

Auxiliary output: 

24V, 100mA electronic fuse 

EXTINGUISHANT RELEASE OUTPUTS 

Extinguishant release output: 

21-28Vdc, rated at 1A for 5 minutes 

Extinguishant release time delay: 

Adjustable 1-60 seconds (1 second steps) 

Extinguishant release duration: 

Adjustable 1-300 seconds (1 second steps) 

Extinguishant release flooding time: 

Adjustable 60-1800 seconds (1 second steps) 

Extinguishant release end-of-line: 

GR System Line Terminator (Item No. 2980-0005) 

FUSES Compliant with IEC (EN60127 Pt2) 

Mains supply fuse (F1): 1A HRC 20mm ceramic; Battery fuse (F2): 5A F 20mm glass; Auxiliary output fuse: 100mA electronic; Sounder circuit fuse: 200mA per 

i

it 

DIMENSIONS & WEIGHT 

Physical Dimensions (W mm x H mm x  D mm): 

Back box = 439 x 276 x 70 approx (Metal); Lid = 467 x 293 x 29 approx (Plastic) 

Weight: 

1.75kg (without batteries) 

Accessory Pack 

1 x Installation Instructions; 1 x User Manual Log Book, 1 x Allen key; 1 x 1A HRC Fuse; 1 x 5A F Fuse; 1 x set of links for PLK1 & PLK2; 1 x set of battery 
connection leads. 

 
 

Introduction 

 

The Gas Release panel is a three zone automatic extinguisher control panel that is compliant with EN12094-1 
and EN54-2. The panel incorporates a 3A, EN54-4 compliant switch mode PSU and a 128 x 64 pixel LCD that 
facilitates system programming. 

 

Installation 

 

Location 

The panel must be mounted indoors on a dry, flat surface in an area that is well ventilated. Ideally the panel 
indicators should be at eye level and the ambient light level should allow the status of any indicators to be clearly 
seen.

 

 

Fixing

 

Note

: The panel’s base PCBs should be removed prior to first fix installation. 

Using the five mounting holes provided, fix the base securely onto a wall. The mounting holes are suitable for 
use with No.8-10, or 4-5mm countersunk screws. Assess the condition and construction of the wall and use 
suitable screw fixings. Any dust or swarf created during the fixing process must be kept out of the enclosure and 
care must be taken not to damage any wiring or components.

 

 

Wiring and Cable Entry 

All wiring should be installed in accordance with the current edition of the IEE Wiring 
Regulations (BS7671), or the relevant national standards. 
The requirement for the mains supply to the panel is fixed wiring, using 3-core cable (no 
less than 1mm

2

 and no greater than 2.5mm

2

), or a suitable three conductor system, fed 

from an isolating switched spur, fused at 3A. 
In order to maintain cable segregation, the incoming mains cable should be fed into the 
panel via the top right hand side knockouts (provided on the base unit). Knockouts 
should be removed with a sharp, light tap using a flat 6mm broadsided screwdriver as 
shown in diagram (see right). Always ensure that if a knockout is removed, the hole is 
filled with a good quality 20mm cable gland. Any unused knockouts must be securely 
blanked off. 

WARNING: DO NOT ATTEMPT TO CONNECT THE MAINS SUPPLY TO THE POWER SUPPLY PCB UNTIL 
ALL PCBs ARE SECURELY INSTALLED IN THE ENCLOSURE. 
 
Connecting Mains Supply to the Power Supply PCB 

Terminate the mains cable at the Power Supply PCB connector CONN1 (see Figure 1 below). 

 
 
 
 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 1 – Power Supply PCB Layout and Connection Details 

“ Our aim is to provide 

 

Consistently Excellent Service ’

  in the eyes of our customers ”

 

 

MAN1807 

Page 3 of 3 