Amit AMR-OP60  SERIES Скачать руководство пользователя страница 1

 

amr-op60xx_g_en_100 

AMR-OP60/xx 

 

Programmable on-wall controller 

Operation manual 

Version 1.00 

 

Содержание AMR-OP60 SERIES

Страница 1: ...amr op60xx_g_en_100 AMR OP60 xx Programmable on wall controller Operation manual Version 1 00...

Страница 2: ...ges must be copied without any changes 2 All redistributed copies must retain the AMiT spol s r o copyright notice and any other notices contained in the documentation 3 This document must not be dist...

Страница 3: ...23 7 2 1 Variant 1 23 7 2 2 Variant 2 24 7 2 3 Variant 3 25 7 3 User s menu 26 Menu items 26 7 4 Configuration menu 30 Menu items 30 7 4 1 Communication settings 32 7 5 Screen saver 36 7 6 Communicat...

Страница 4: ...AMR OP60 XX amr op60xx_g_en_100 4 49 12 Ordering information and completion 47 12 1 Completion 47 13 Maintenance 48 14 Waste disposal 49...

Страница 5: ...anges 100 13 5 2014 New document Related documentation 1 DetStudio Development Environment Help 2 Data sheet AMR OP60 xx file amr op60xx_d_en_xxx pdf 3 Application Note AP0016 Principles of using RS48...

Страница 6: ...ed by four buttons ABB Elektro Praga Time Time Arbo Element design RS485 line without galvanic separation Power supply 24 V DC User programming in DetStudio EsiDet environment is possible MODBUS RTU o...

Страница 7: ...ime from power on Measurement accuracy is reduced to 2 C during this time Overvoltage protection Transil 600 W Galvanic separation No Terminating resistor No Maximum wire length 1200 m 19200 bps Max n...

Страница 8: ...int 2 WAGO 243 204 Wire cross section 0 6 mm2 to 0 8 mm2 Operating temperature range 10 C to 50 C Storage temperature range 20 C to 70 C Maximum ambient humidity 95 non condensing Application software...

Страница 9: ...9 amr op60xx_g_en_100 2 2 Recommended drawing symbol Following drawing symbol is recommended for AMR OP60 xx on wall controller 1 2 3 4 PWR RS485 AMR OP60 xx V G B A Fig 2 Recommended drawing symbol f...

Страница 10: ...3 Radiated radio frequency electromagnetic field immunity test 1000 MHz to 2100 MHz 10 V m EN 61000 4 3 2006 Electromagnetic compatibility EMC Part 4 3 Radiated radio frequency electromagnetic field i...

Страница 11: ...t Result EN 60068 2 1 2007 Environmental testing Part 2 1 Test A Cold Complies EN 60068 2 2 2007 Environmental testing Part 2 2 Test B Dry heat Complies EN 61000 4 29 2000 Electromagnetic compatibilit...

Страница 12: ...ted in chapter 2 Technical parameters Fig 3 Location of power supply connector Number Meaning 1 Power supply pole Each pole of the connector has 4 connection points Power supply can be connected to an...

Страница 13: ...100 1 2 3 4 PWR RS485 AMR OP60 xx V G B A GND 24V Ext power supply Fig 4 Power supply wiring example It is recommended to connect in one point the GND terminal with switchboard PE terminal when instal...

Страница 14: ...ected to any connection point see Fig 9 Connecting to connection points Pole Label Meaning 3 B RS485 line signal B 4 A RS485 line signal A On wall controller is connected with superior control system...

Страница 15: ...one pair of wires to the positive terminal one pair of wires to the negative terminal and one pair of wires to connect RS485 line AMR OP60 G V B A Fig 7 Connecting structured cabling to poles of cont...

Страница 16: ...ine termination Number Meaning 1 External terminating resistor Any connection point of each pole of RS485 line can be used for connection of external resistor see following figure Fig 9 Connecting to...

Страница 17: ...erminating resistor Activity on RS485 line is indicated on LCD If it is not specified other way in control system via Guard Time icon is displayed 30 s after communication interruption indicating comm...

Страница 18: ...with the connector that can be easily pulled out from the motherboard after releasing latches On wall controller motherboard is connected to mounting box KU68 Pay attention to the correct orientation...

Страница 19: ...r source properties and wiring layout this requirement can be revised Connect the negative supplying terminal of controller G to the switchboard PE terminal at the power source If inlet wires are led...

Страница 20: ...lowed it will be displayed after pre set time of controller inactivity 7 1 Basic screen The design of the screen depends on selected application variant Variant is set by the service organization duri...

Страница 21: ...ested temperature Temperature is sent by the superior control system During correction change hyphens are displayed until new requested value is received from the superior control system Value could b...

Страница 22: ...hens are displayed until new requested temperature value is received from the superior control system In the icons line there is an icon displayed all the time that informs about possibility to call u...

Страница 23: ...ber Meaning 1 Icon showing what room mode is set By pressing button under icon you can switch between three room modes Icon Meaning Description Comfort Is regulated to constant comfort temperature Att...

Страница 24: ...egulated to constant comfort temperature Attenuation Is regulated to constant power saving temperature Auto Is regulated according to time plan adjusted by correction value By pressing button under ic...

Страница 25: ...ction By pressing button under icon 1 you can switch between three room modes Icon Meaning Description Comfort Is regulated to constant comfort temperature Attenuation Is regulated to constant power s...

Страница 26: ...ser menu can be called by pressing button under icon Fig 21 Calling user menu Number Meaning 1 Icon above the button for calling user menu Menu items Fig 22 User s menu Number Meaning 1 Menu items 2 I...

Страница 27: ...items can be selected from the menu Brightness Contrast Language Display Info The display brightness can be set by item Brightness Fig 23 Brightness adjustment Number Meaning 1 Set brightness level 2...

Страница 28: ...f buttons under icons 2 is as follows Icon Meaning Lower contrast level Higher contrast level Item Language allows switching between Czech and English texts on on wall controller Fig 25 Language selec...

Страница 29: ...2 is as follows Icon Meaning Lower time value Higher time value Following values can be set Value Meaning 1 Screensaver is off 10 to 120 Screen saver time delay in seconds By selecting item Info the a...

Страница 30: ...on menu Number Meaning 1 Icon above the button for calling configuration menu Setting of on wall controller software and hardware should be performed strictly by service company Wrong configuration se...

Страница 31: ...an be found in chapter 7 4 1 Communication settings Via item FW setting the one of three variants of AMR OP60 xx can be selected see chapter 7 2 Mode icons Fig 30 Variant selection Number Meaning 1 Se...

Страница 32: ...Meaning Leaving the screen Reduce correction value Increase correction value Confirmation of correction value Sensor correction value can be set within the range 1 5 C to 1 5 C 7 4 1 Communication set...

Страница 33: ...lected ARION MODBUS Fig 33 Communication protocol selection Number Meaning 1 Selected communication protocol 2 Icons above the buttons for working with screen Meaning of buttons under icons 2 is as fo...

Страница 34: ...alue Increase address value Confirmation of selected variant Via item Baud rate the communication speed within selected communication network can be set All to the network connected devices must have...

Страница 35: ...rotocol was selected Parity can be set by this item Fig 36 Setting parity for MODBUS protocol Number Meaning 1 Selected parity 2 Icons above the buttons for working with screen Meaning of buttons unde...

Страница 36: ...er Meaning 1 Measured temperature 2 Requested temperature 3 Time of superior system If after power supply connection or controller restart the time setting is not received from superior control system...

Страница 37: ...AMR OP60 XX 37 49 amr op60xx_g_en_100 Fig 40 Communication interruption during active screen saver Icon is displayed until controller receives valid data from the superior control system...

Страница 38: ...erior control system reads out registry values by writing value True to bit n 1 of digital output channel DO 1 it sets bit n 1 of the digital input channel to value False 8 2 Digital outputs Single bi...

Страница 39: ...or the Variant 3 In other variants this bit is not used 4 5 6 Fan mode Bit 6 Bit 5 Bit 4 Meaning 0 0 0 Device is OFF 0 0 1 Level 1 0 1 0 Level 2 0 1 1 Level 3 1 0 0 Automat Applies only for the Varian...

Страница 40: ...terruption on wall controller does not have a valid value of room and fan mode setting button status required temperature In case of on wall controller restart the correction value will be zeroed as w...

Страница 41: ...ption Zero value will result in permanent disconnection and Error state Baud Rate 5 R W EEPROM EEPROM baud rate Parity 6 R W EEPROM EEPROM parity Address 7 R W EEPROM EEPROM address System Status 8 R...

Страница 42: ...pplies only for the Variant 2 In other variants this bits are not used 7 Status of DI input Ni1000 contact Correction Float 104 105 R W Correction Range 100 to 100 with floating point Requested temper...

Страница 43: ...within 30 s the icon is displayed automatically see chapter 7 6 Communication interruption Bits 0 to 7 of the Status registry are set to value True During the communication interruption on wall contr...

Страница 44: ...from PC via DetStudio AMRconfig from application program via configuration menu see chapter 7 4 1 from service application via service menu see chapter 10 3 On wall controller must be connected to the...

Страница 45: ...rvice menu Following items can be set via service menu Brightness brightness intensity change Contrast change of display contrast Serial interface communication parameters Language Can be set only in...

Страница 46: ...ut external terminating resistor Item Set value Network type ARION Address 1 Baud rate 38400 bps Viewing variant Variant 1 Correction 0 0 C Display Set value Brightness 100 Contrast 50 Language Czech...

Страница 47: ...e chapter 12 1 Completion xx indicates colour design of the product Available versions are listed in datasheet RR 120R External termination resistor for RS485 12 1 Completion Part Quantity On wall con...

Страница 48: ...d be cleaned with soft cloth Dirty covers should be washed with gently wet cloth with mild soap solution and then wiped with dry cloth Never use tough cleaning cloth or preparations containing sharp p...

Страница 49: ...sal The disposal of electronic equipment is subject to the regulations on handling electrical waste The equipment must not be disposed of in common public waste It must be delivered to places specifie...