Outdoor LoRa Data Logger
10
1.6 Hardware Installation
Hereunder list the available H/W ports of OOT550:
•
SIM Slot:
1* nano-SIM (4FF)
•
Analog Input:
3* AI ports (AI1,AI2 supports 0-10V / 4-20mA; AI3 supports 0-20V / 0-40mA)
•
Digital Input:
2* DI ports (isolated,
“Logic 1”: 2V~25V, “Logic 0”: 0~1V or floating;
supports Pulse Counter, Dry Contact)
•
Digital Output:
1* DO port (isolated, Non-Relayed Output,
Maximum 24V/300mA
)
•
Field Bus:
1* RS-485 for Modbus RTU
•
Configuration :
1* Micro USB port for device configuration
•
Wake-up Port
: 1* dedicated DI for external device wake-up triggering.
•
Power Source :
4000mAh 3.6V Li-SOCL2 battery (ER18505, A Size)
, or
external 5V~12V DC power.
This section describes how to install and configure the hardware.
1.6.1 Open the Top Cover
The OOT550 series is design for universal data logging use. There are various interfaces for connecting to your
field devices, and enclosed with an IP65 grade enclosure. All the connection cables to the field devices must be
wired properly through the M16 connectors.
Therefore, prior to connecting and configuring the OOT550, you have to open the top cover to get access to
the control board.
Unscrew the four screws and remove the top cover to the side carefully.
You can see there are lots of hardware connectors available for you to configure. There are two spring-type
Terminal Blocks, a nano-SIM slot, Battery Stand, Power Socket and Switch, etc...