Controls Overview
3.2.3 Tank Settings
This screen sets the basic parameters for any installed
tank level switch. The switches must be dry contact
(open or closed circuit) type switches. The logic for
switch condition to run condition can be set according to
the switch setup.
•
Enable/Disable: Sets whether the tank sensor is
available to the system or not.
•
Stop Delay: The tank level switch must remain in the
“no run condition” for the specified delay time before
the system will take action from the input. This is intended to eliminate nuisance shutdowns due to
water turbulence.
•
Shutdown Delay: This value sets the time delay between when the product tank is full and when
the system shuts down. This provides an opportunity for the tank to catch up without a premature
shutdown.
•
Automatic Restart: Sets whether the system will automatically restart after the sensor condition has
cleared.
•
Restart Delay: With automatic restart enabled and after a tank switch shutdown, the switch must
remain in the run position for the delay time before any action is taken. This is intended to stagger
restart and prevent premature restart.
•
Switch for Run: This option allows the circuit logic for the switch to be changed. For example, if
Open is selected the switch must provide an open circuit for a run condition.
3.2.4 Startup Settings
This screen sets the parameters for system startup. Touch the General or Air Bleed tab to open the
appropriate sub-screen.
3.2.4.1 General
•
Startup Feed Pressure: This is the minimum pressure
that must be reached in the housing for startup event
to continue.
•
Startup Feed Pressure Delay: This is the time allowed
for the system to reach the pressure setpoint. If the
timer expires before the pressure is reached startup
will be aborted.
•
Startup Speed: This is the minimum cleaning
assembly speed that must be reached for the startup
event to continue.
•
Startup Speed Delay: This is the time allowed for the cleaning assembly to reach the minimum
speed requirement. If the timer expires before the RPM is reached startup will be aborted.
•
Startup Time: Once both minimum setpoints are reached the system will dwell for the time
specified. This will allow the system to clean and then purge any contaminates off the screen before
entering normal operation.