![amiad ABF-15000 Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/amiad/abf-15000/abf-15000_installation-operation-and-maintenance-instructions_2932253010.webp)
ABF-15000 OL
910101-000320 / 09.2017
Page 10 of 19
INSTALLATION AND START-UP INSTRUCTIONS
Mechanical Considerations
1. Select a convenient location for the installation of the filter where operation and maintenance will be optimum.
2. It is recommended to prepare a beam or any other arrangement, which will allow hanging a crane for opening the filter.
3. Install the filter vertically. Please note that a minimum clearance of 700 mm (28 In.) is required in order to allow disassembly of
the unit.
4. Make sure that the direction of the flow is as indicated by the arrow marked on the filter housing. (Flow outlet will always be from
the side; flow inlet is from the bottom).
5. If possible, prior to installing the filter, flush the main line, at the connection point thoroughly, in order to remove large objects,
this may damage the filters internal mechanism.
6. Connect a 3" drainage pipe to the exhaust valve (#14). The maximum length of the drainage pipe will be 40 meters (120 feet).
Please note, that no restriction is allowed on the drainage pipe. For special applications, please consult the manufacturer.
Electrical Considerations
1. Connect the appropriate electrical power supply to the control board and the interconnections between the control board and
the electrical components on the filter, according to the wiring diagram provided.
2. Install fuses as noted on the electrical schematic and ensures that all electrical connections are well insulated.
3. The electrical wires (conduit) connecting the control board and the filter should be of sufficient length to enable disassembly of
the drive unit from the lid without disconnecting these wires.
Start-up Considerations
1. Switch on the main circuit breaker.
2. Press the "TEST" push-button and check the direction in which the motor is rotating. The motor should rotate the brush shaft
clockwise. If it is rotating in the other direction - change the direction by swapping the phase connections.
3. Slowly open the valve at the inlet of the filter. If possible with an outlet valve closed and a by-pass valve open, and repeat a
manual flushing.
4. Open the outlet valve gradually and bring the filter to normal working condition.
5. Check that the PDS is properly functioning by draining its low-pressure tube. Draining is done by means of the 1/4" valve. Closing
the valve for at least 3 seconds will cause the PDS to send an electric signal to the control board and automatic cleaning will
begin.
6. The cleaning operation should be for 15 seconds and full flow out of the exhaust valve should be observed during this entire
period. After the 15 second cleaning operation, the flow out of the exhaust valve should stop immediately. Be sure to observe
that there is no significant leakage occurring from the exhaust valve once the cleaning operation has completely stopped.