User Manual
_________________________________________________________________
fdfefd fd
© 2019 AMETEK Electronic Systems Protection | Technical Support: 1-800-645-9721 | surgex.com 30
3) Battery setting
(available in all operational modes)
Interface
Description
Battery :
DisChg Protect :
Enable
990 Minute
Batt Test Type :
Short Time :
Till Batt Low
Battery :
DisChg Protect :
Enable
990 Minute
Batt Test Type :
Short Time :
10 Minute
Battery :
DisChg Protect :
Enable
990 Minute
Batt Test Type :
Short Time :
10 Second
1. Dischg Protect :
1.1
Enable :
Battery discharge protection function is enabled. When the
UPS has been continuously operating in “battery/battery test mode”, the
UPS will automatically shut down when the discharge time set by option
1.2 below has expired.
Disable :
Battery discharge protection function is disabled.
1.2
0000 ~ 1500 :
The maximum discharge time ranging from 0 to 1500 mi-
nutes. When “Dischg Protect” is enabled the UPS will shut down to
protect the battery after backup time arrives. If “Dischg protect” is dis-
abled then this setting is not functional. The default value for this setting
is 990 minutes.
2. Batt Test Type :
2.1 Short Time :
Battery test will last for a duration of 10 seconds.
2.2 Long Time :
The duration of the battery test can be set to 01 ~ 99
minutes.
2.3 Till Batt Low :
Battery test will not stop until the battery voltage
is low.