© 2019 AMETEK Electronic Systems Protection | Technical Support: 1-800-645-9721 | surgex.com 27
3-6-2-4. Information
Information displays the value and status of all parameter settings. Press the “UP” or “DOWN” button to explore
the pages.
Bypass: 1/6 ECO: 2/6 Output: 3/6
Status:
Open
Status:
Open
Volt:
208V
Enable
HighLoss V:
232V
Freq:
Auto
HighLoss V: 264V LowLoss V: 184V CVCF: Disable
LowLoss V: 110V HighLoss F: 52Hz
HighLoss F: 54Hz LowLoss F: 48Hz
LowLoss F : 46Hz
Battery : 4/6 UPS Info : 5/6 Others : 6/6
Backup Time : UPS Model : XXXX Hot Standby :
990 Minute
DSP Ver :
XXXX
Disable
Batt Test Type :
MCU Ver :
XXXX
Bypass Mute :
Short Time :
Unit Name :
Disable
10 Second
XXXXXXXXX
Batt
Mute :
Manufacturer :
Disable
XXXXXXXXX
Fault Mute :
Disable
3-7-2-5 . Setting
This menu is used to configure the parameter settings or to do the calibrations.
Setting : Bypass
Output
Battery
Calibration
Others
NOTE: Some settings will only be available in certain operation modes. If the setting is not available in the current
Mode, the LCD will show the message “Item cannot be set in this mode”. Press any button or wait several seconds
for the message to disappear.