3-6-2-2. Control
Control:
Turn On Batt
Test Mute
Para Unlock
NOTE 1: “Para Unlock” appears only when a parallel communication failure occurs.
NOTE 2: “Turn On” will be displayed if UPS is not turned on. “Turn Off” will be displayed if UPS is turned on.
Generally speaking, these two messages will not be displayed at the same time or in all operation modes.
1) Turn On/Turn Off
This item is for turning on/off the UPS;
a) In Bypass mode the LCD will display “Turn On” in the control menu. If it is selected and confirmed, the
UPS will transfer to AC mode or to converter mode or to battery mode according to the setting and input
status.
Control:
Line Mode
Turn On Turn On?
Batt Test IP: 208.0V / 50.0Hz
Mute Yes OP: 208.0V / 50.0 Hz
Para Unlock No Batt: 273.0V / 99%
Load:
100%
NOTE: The UPS may be turned on by simply pressing the “ON/ENTER” button in the home page. It’s
not necessary to enter the control menu to turn on the UPS.
b) In AC mode or converter mode or battery mode, the LCD will display “Turn Off” in the control menu.
If it is selected and confirmed, the UPS will transfer to bypass mode or shut down.
Control:
Bypass Mode
Turn On Turn Off?
Batt Test IP: 208.0V / 50.0Hz
Mute Yes OP: 208.0V / 50.0 Hz
Para Unlock No Batt: 273.0V / 99%
Load:
0%
NOTE: The UPS may be turned off by simply pressing the “OFF/ESC” button in the home page. It’s
not necessary to enter the control menu to turn off the UPS.