Local Operation
M370430-01 Rev B
3-25
3
Alarm Output Latching
When an alarm is triggered, the output will be disabled with the
exception of the Fan alarm. When an alarm is cleared, the alarm output
latch determines if the output should be re-enabled to the state before the
alarm occurred or if the output should remain in the off state.
Where setting the bit position (1) of an alarm latch will result in output
latching to the off state when the alarm is cleared and if cleared (0)
output will be re-enabled to the state before the alarm triggered.
To define the values for the bit position you determine which alarms you
want to latch. Read the value for this bit position from Table 3-6 and
sum them together. The result is the alarm last mask, which you should
send with the SCPI command.
For Example:
If you wanted to enable latching for OTP and Foldback you would take
the OTP value of 2 and add it to the foldback value of 256 to get a mask
of 258. This is the value you would send with the SCPI command.
The output latches are accessible through the SCPI command.
The SCPI command (s) for these instructions are:
[:]SYSTem[<channel>]:PROTection:LATCh
The latch command take a single decimal parameter made up of the sum
of the values for the alarms to determine if they are to be latched in the
off state on clearing. See Table 3-6 for the values associated with each
latchable alarm.
Table 3-6
Alarm Latch Bit Positions
Alarm
Bit
Position
Value
AC Fail
0
1
Over Temperature Protection (OTP)
1
2
Over Temperature Protection (OTP) Slave
(1700 Watt only)
3
4
Foldback
8
256
Содержание Sorensen XG
Страница 2: ......
Страница 22: ...Contents xx M370430 01 Rev B ...
Страница 23: ...1 Introduction Chapter 1 Introduction describes the features of the XG XTR Family Programmable DC Power Supply ...
Страница 94: ...Local Operation 3 46 M370430 01 Rev B Figure 3 4 Split Supply Operation Power Supply Power Supply Common Load ...
Страница 96: ...Local Operation 3 48 M370430 01 Rev B Figure 3 5 Series Operation ...
Страница 102: ...Local Operation 3 54 M370430 01 Rev B ...
Страница 210: ...Remote Operation 5 76 M370430 01 Rev B ...
Страница 248: ...Communications Options 6 38 M370430 01 Rev B 9 In the Setup Type window choose Typical and click Next ...
Страница 249: ...Communications Options M370430 01 Rev B 6 39 6 10 Check that your Settings are correct and then click Install ...
Страница 256: ...Communications Options 6 46 M370430 01 Rev B 9 In the Setup Type window choose Typical and click Next ...
Страница 276: ...Communications Options 6 66 M370430 01 Rev B ...
Страница 358: ...Specifications C 12 M370430 01 Rev B Figure C 2 XG XTR 850 Watt Mechanical Dimensions 60 V to 600 V Models ...
Страница 359: ...Specifications M370430 01 Rev B C 13 Figure C 3 XG XTR in Full Rack Mechanical Dimensions 6 V to 40 V Models ...
Страница 361: ...Specifications M370430 01 Rev B C 15 Figure C 5 XG XTR in Full Rack Mechanical Dimensions 60 V to 600 V Models ...
Страница 364: ...Specifications C 18 M370430 01 Rev B Figure C 9 XG850 Low Voltage Model Dimensions Top Side and Rear ...
Страница 365: ...Specifications M370430 01 Rev B C 19 Figure C 10 XG850 Medium and High Voltage Models Dimensions Top and Rear ...
Страница 371: ...Rack Mount Options and Installation Instructions M370430 01 Rev B D 5 Figure D 3 RM XG2 RM XTR2 Rack Rails ...
Страница 377: ...Rack Mount Options and Installation Instructions M370430 01 Rev B D 11 Figure D 10 Installing Chassis ...
Страница 378: ...Rack Mount Options and Installation Instructions D 12 M370430 01 Rev B ...
Страница 381: ......