Installation
2-16
M370430-01 Rev B
3.
Connect one end of the shield of the twisted pair wire to the
chassis ground point on the power supply.
4.
Connect the positive sense line (+SNS) from the positive
regulation point as close as possible to the load terminals to
pin J1. 1.
5.
Connect the negative sense line (-SNS) from the return of the
load to pin J1-6.
To compensate for losses in power leads connected to the output,
the power supply provides sense connections beside the output
terminals. With remote sense leads in place, the power supply
regulates to the displayed voltage at the point where the sense lines
are connected to the output leads. With the sense lines disconnected,
the power supply regulates the voltage at the output terminals.
CAUTION: Equipment damage
Do not operate the power supply with sense lines connected to the load without
also connecting the load power leads to the output terminals.
CAUTION: Reverse polarity
Avoid reversing positive (+) and negative (-) sense connections. When using
remote sense to compensate for load line losses, ensure that the positive sense
line is connected to the positive load terminal and the negative sense line is
connected to the negative load terminal. Do not reverse these connections or the
power supply may be damaged.
Important:
Long load leads with large capacitance at the load and remote
sensing can cause voltage instability due to inductance of the load leads.
Measures to reduce inductance and/or capacitance (raising resonant frequency)
or using local sense can be beneficial in stabilizing the system.
Содержание Sorensen XG
Страница 2: ......
Страница 22: ...Contents xx M370430 01 Rev B ...
Страница 23: ...1 Introduction Chapter 1 Introduction describes the features of the XG XTR Family Programmable DC Power Supply ...
Страница 94: ...Local Operation 3 46 M370430 01 Rev B Figure 3 4 Split Supply Operation Power Supply Power Supply Common Load ...
Страница 96: ...Local Operation 3 48 M370430 01 Rev B Figure 3 5 Series Operation ...
Страница 102: ...Local Operation 3 54 M370430 01 Rev B ...
Страница 210: ...Remote Operation 5 76 M370430 01 Rev B ...
Страница 248: ...Communications Options 6 38 M370430 01 Rev B 9 In the Setup Type window choose Typical and click Next ...
Страница 249: ...Communications Options M370430 01 Rev B 6 39 6 10 Check that your Settings are correct and then click Install ...
Страница 256: ...Communications Options 6 46 M370430 01 Rev B 9 In the Setup Type window choose Typical and click Next ...
Страница 276: ...Communications Options 6 66 M370430 01 Rev B ...
Страница 358: ...Specifications C 12 M370430 01 Rev B Figure C 2 XG XTR 850 Watt Mechanical Dimensions 60 V to 600 V Models ...
Страница 359: ...Specifications M370430 01 Rev B C 13 Figure C 3 XG XTR in Full Rack Mechanical Dimensions 6 V to 40 V Models ...
Страница 361: ...Specifications M370430 01 Rev B C 15 Figure C 5 XG XTR in Full Rack Mechanical Dimensions 60 V to 600 V Models ...
Страница 364: ...Specifications C 18 M370430 01 Rev B Figure C 9 XG850 Low Voltage Model Dimensions Top Side and Rear ...
Страница 365: ...Specifications M370430 01 Rev B C 19 Figure C 10 XG850 Medium and High Voltage Models Dimensions Top and Rear ...
Страница 371: ...Rack Mount Options and Installation Instructions M370430 01 Rev B D 5 Figure D 3 RM XG2 RM XTR2 Rack Rails ...
Страница 377: ...Rack Mount Options and Installation Instructions M370430 01 Rev B D 11 Figure D 10 Installing Chassis ...
Страница 378: ...Rack Mount Options and Installation Instructions D 12 M370430 01 Rev B ...
Страница 381: ......