Installation
Asterion DC Series
2-28
Size
Temperature Rating of Copper Conductor
AWG
60°C
75°C
90°C
Types: TW, UF
Types: RHW,
THHW, THW,
THWN, XHHW,
USE, ZW
Types: TBS, SA,
SIS, FEP, FEPB,
MI, RHH, THHN,
THHW, XHH,
XHHW
Current Rating, A(RMS)
18
−
−
14
16
−
−
18
14
15
20
25
12
20
25
30
10
30
35
40
8
40
50
55
6
55
65
75
4
70
85
95
3
85
100
115
2
95
115
130
1
110
130
145
0
125
150
170
00
145
175
195
000
165
200
225
0000
195
230
260
Table 2-7. Minimum Wire Size
When determining the optimum cable specification for your power applications, the
same engineering rules apply whether at the input or output of an electrical device.
Therefore, this guide applies equally to the input cable and output cable for this
power source and application loads. Power cables must be able to safely carry
maximum load current without overheating or causing insulation degradation. It is
important to power source performance to minimize IR (voltage drop) loss within the
cable. These losses have a direct effect on the quality of power delivered to and from
the power source and corresponding loads.
When specifying wire gauge, consider derating due to operating temperature at the
wire location. Wire gauge current capability and insulation performance drops with
the increased temperature developed within a cable bundle and with increased
environmental temperature. Therefore, short cables with derating of gauge size and
insulation properties are recommended for power source applications.
Be careful when using published commercial utility wiring codes. These codes are
designed for the internal wiring of homes and buildings and accommodate the safety
factors of wiring loss, heat, breakdown insulation, aging, etc. However, these codes
consider that up to 5% voltage drop is acceptable. Such a loss directly detracts from
Содержание Sorensen Asterion DC Series
Страница 1: ...M330460 01 Rev D 1 Asterion DC Series Operation Manual...
Страница 2: ...Contents Asterion DC Series ii This page intentionally left blank...
Страница 23: ...Asterion DC Series Overview M330460 01 Rev D 1 7 Figure 1 2 Auto range Models Characteristics...
Страница 38: ...Overview Asterion DC Series 1 22 This page intentionally left blank...
Страница 43: ...Asterion DC Series Installation M330460 01 Rev D 2 5 Figure 2 1 Rack mounting 1U Models...
Страница 44: ...Installation Asterion DC Series 2 6 Figure 2 2 Rack Mounting 2U Chassis...
Страница 48: ...Installation Asterion DC Series 2 10 Figure 2 4 Installation Drawing Enhanced front panel version 2U Models...
Страница 49: ...Asterion DC Series Installation M330460 01 Rev D 2 11 Figure 2 5 Rear Panel View 1U Models...
Страница 50: ...Installation Asterion DC Series 2 12 Figure 2 6 Rear Panel View 1U Models w EtherCAT Option...
Страница 51: ...Asterion DC Series Installation M330460 01 Rev D 2 13 Figure 2 7 Rear Panel View 1U Models w GPIB Option...
Страница 52: ...Installation Asterion DC Series 2 14 Figure 2 8 Rear Panel View 2U Chassis...
Страница 83: ...Asterion DC Series Installation M330460 01 Rev D 2 45 This page intentionally left blank...
Страница 84: ......
Страница 144: ...Calibration Asterion DC Series 3 60 Figure 3 114 Parallel Connection 3 Chassis...
Страница 145: ...Asterion DC Series Calibration M330460 01 Rev D 3 61 Figure 3 115 Parallel Connection 2 Chassis...
Страница 148: ...Calibration Asterion DC Series 3 64 Figure 3 117 Series Connection...
Страница 149: ...Asterion DC Series Calibration M330460 01 Rev D 3 1 This page intentionally left blank...
Страница 151: ...Asterion DC Series Calibration M330460 01 Rev D 4 3 This page intentionally left blank...
Страница 152: ......
Страница 157: ...M330460 01 www powerandtest com This page intentionally left blank...