A01-00104 Rev A

6.0 TROUBLESHOOTING

The troubleshooting information provided in this section should help you 

discover the cause of most commonly encountered difficulties. Before follow

-

ing the troubleshooting steps provided, be certain that you have verified the 

following items:

•  The UPM should be plugged into a properly working outlet.
• 

The line voltage to the UPM is within specified boundaries.

•  The circuit breaker on the rear panel of the UPM has been reset.
•  The battery enable plug(s) is installed.

Problem

Possible Cause

Action you should take

UPM does not 

power up and has 

no audible alarm

1. On/Off Button not pressed 

long enough.

2. No incoming line voltage 

or voltage too high or too 

low.

3. UPM input power cord is 

not plugged in.

4. Rear panel circuit breaker 

is tripped.

1. Press and hold the On/Off switch 

for 3 seconds min.

2. Check wall socket and test for 

proper line voltage.

3. Plug in input power cord.

4. Reduce load and reset circuit 

breaker.

UPM Over-

load LED’s are 

illuminated and 

continuous audible 

alarm sounds

UPM is overloaded.

Reduce load by removing the least 

critical load items from the UPM 

output.

Low/Replace 

Battery LED is 

illuminated

Battery voltage is too low or 

battery is dead.

Recharge battery for at least six 

hours and reset UPM. If LED is still 

illuminated, replace the battery.

Site Wiring Fault 

LED is illuminated

Site wiring problem.

Contact a qualified electrician to 

verify wiring at this site.

Backup time is 

less than expected

Battery is not fully charged or 

battery is dead.

Recharge battery for at least six 

hours and retest back up time.

UPM is normal, 

but the computer 

will not turn on.

Computer input power cord 

is loose or not connected.

Connect the power input power 

cord.

Содержание ABCE1002-11R

Страница 1: ...Security II Rackmount Series Uninterruptible Power Manager For use with 700VA 1000VA 1440VA 2200VA and 3000VA...

Страница 2: ...2 A01 00104 Rev A 1 0 Introduction 6 2 0 Safety Instructions 8 3 0 Installation 12 4 0 Operation 17 5 0 Maintenance 22 6 0 Troubleshooting 27 7 0 Warranty 29 8 0 Specifications 30 TABLE OF CONTENTS...

Страница 3: ...nsistently connected to AC mains power except during utility outages Products regularly and intentionally disconnected from AC mains power will experience substantially reduced battery life The standa...

Страница 4: ...ditions that can cause operator injury and or equipment damage Other warning symbols may appear along with the Danger and Caution symbol and are used to specify special hazards These warnings describe...

Страница 5: ...5 A01 00104 Rev A Alternating Current Refer to instruction manual booklet Two person lift...

Страница 6: ...ou have any questions at all please feel free to contact our technical support team by phone 1 800 369 7179 or email us at service powervar ametek com We are a global provider of power management solu...

Страница 7: ...mped ance isolation transformer it completely eliminates common mode neutral to ground voltages that are a constant threat to the reliable operation of microprocessor based systems When AC power is pr...

Страница 8: ...are maintenance free Proper disposal of batteries is required Refer to your local codes for disposal of batteries UPM Rating Quantity and Battery Rating 700 VA 4 X 23W 12 VOLT 1000 VA 4 X 23W 12 VOLT...

Страница 9: ...support device Do not use this UPM near or around flammable gases Do not use this UPM within oxygen enriched atmospheres Do not disassemble the UPM UPM is CLASS 1 equipment Do not attempt to power th...

Страница 10: ...ging at its quick connectors when maintenance or service work inside the UPM is necessary Do not dispose of batteries in a fire batteries may explode Do not open or mutilate batteries Doing so may rel...

Страница 11: ...mful interference to radio communications However there is no guaran tee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio and or...

Страница 12: ...s unit is shipped with the internal batteries disconnected Before starting the UPM please follow these battery connection instructions 1 Remove UPM from the box 2 Attached included outlet cord and plu...

Страница 13: ...inserting the battery plug s before pressing the ON switch on the UPM front panel If you ship the UPM to another location at a later date disconnect the battery plug s first to ensure that safety is m...

Страница 14: ...3 Store the carton for future use Place the unit in a protected area that has adequate airflow and is free of humidity flammable gas and corrosion NOTE Before installation please read and understand t...

Страница 15: ...using the 8 screws provided 6 For 4U UPMs attach 2 angled mounting brackets to each side of the UPM using the 16 screws provided 7 Lift the battery cabinets and UPM onto the mounting rails and slide...

Страница 16: ...of the equipment 2 Send a copy of the damage claim within 15 days to your service representative WARNINGS Use all supplied mounting hardware on each UPM and External Battery Cabinet NEVER depend on d...

Страница 17: ...no incoming AC present When the UPM is on pressing the On Off button for more than 2 seconds will turn off the UPM output power Test Silence Button The Test Silence button is a dual function control P...

Страница 18: ...of the UPM if it is connected to an improperly wired AC receptacle This is to indicate a missing safety ground wire or a reversal in phase and neutral wiring If the SF is displayed on the front panel...

Страница 19: ...M by pressing and holding the front panel On Off switch for 3 seconds Operational Tests Observe the front panel of the UPM The following table shows system status behavior UPM LED DISPLAY UNIT STATUS...

Страница 20: ...p function by pressing the Test Silence button on the front pan el During this test the Battery LED on the front panel should briefly illuminate It is also possible to test the backup function by unpl...

Страница 21: ...test periodically The UPM is shipped with a charged battery but some discharge naturally occurs during storage and shipment You may use the UPM immediately but you should realize that backup time may...

Страница 22: ...rientation The batteries are designed to last from two to five years Their actual life span will depend on several factors including how often power outages occur how long power outages last and the t...

Страница 23: ...able parts are contained in this UPM Do not remove any cover other than the front battery access panels A battery even a depleted one can deliver very high currents when short circuited There is a dan...

Страница 24: ...running NOTE Changing the batteries in this UPM is designed to be a safe and simple procedure Batteries may be replaced while the UPM is on and providing power to the connected load You should remembe...

Страница 25: ...The following precautions should be observed when working with batteries Remove watches rings or other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or...

Страница 26: ...uction for Returning a Depleted Battery Pack for instructions on returning depleted battery s to AMETEK Powervar A01 00074 Rev C Battery packs can be replaced without turning off the power or disrupti...

Страница 27: ...cuit breaker is tripped 1 Press and hold the On Off switch for 3 seconds min 2 Check wall socket and test for proper line voltage 3 Plug in input power cord 4 Reduce load and reset circuit breaker UPM...

Страница 28: ...5 A ABCE1442 11R ABCE1442 11RMED 250 VAC 12 5 A ABCE1442 22R ABCE1442 22RMED 250 VAC 6 3 A Technical Support The Company provides technical product support during our regular business hours of 8 00 a...

Страница 29: ...ipment on the batteries This warranty is limited to repairing replacing or refurbishing at our option any defective component circuit board or module within the Product This warranty is limited to the...

Страница 30: ...nput Current 8 70 Amps 8 70 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 5 85 5 25 Amps 5 85 5 25 Amps Output Regulation On...

Страница 31: ...20 15 12 10 9 Internal 1 E4804 12 1030 480 292 188 143 110 85 77 66 64 Internal 2 E4804 12 1930 870 532 338 263 200 155 142 122 119 Internal 3 E4804 12 2830 1260 772 488 383 290 225 207 178 174 Inter...

Страница 32: ...oltage 120 120 Input Current 8 70 Amps 8 70 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 5 85 5 25 Amps 5 85 5 25 Amps Outp...

Страница 33: ...E4804 12 1930 870 532 338 263 200 155 142 122 119 Internal 3 E4804 12 2830 1260 772 488 383 290 225 207 178 174 Internal 4 E4804 12 3730 1650 1012 638 503 380 295 272 234 229 Internal 5 E4804 12 4630...

Страница 34: ...iciency w o Charger 91 Input Voltage 230 Input Current 4 54 Amps Output Voltage 230 Output Current VA Watts 3 05 2 75 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On M...

Страница 35: ...441W 80 504W 90 567W 100 630W Internal Batteries Only 130 90 52 38 23 20 15 12 10 9 Internal 1 E4804 12 1030 480 292 188 143 110 85 77 66 64 Internal 2 E4804 12 1930 870 532 338 263 200 155 142 122 11...

Страница 36: ...Efficiency w o Charger 91 Input Voltage 230 Input Current 4 54 Amps Output Voltage 230 Output Current VA Watts 3 05 2 75 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation...

Страница 37: ...143 110 85 77 66 64 Internal 2 E4804 12 1930 870 532 338 263 200 155 142 122 119 Internal 3 E4804 12 2830 1260 772 488 383 290 225 207 178 174 Internal 4 E4804 12 3730 1650 1012 638 503 380 295 272 2...

Страница 38: ...120 120 Input Current 12 0 Amps 12 0 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 8 35 7 5 Amps 8 35 7 5 Amps Output Regul...

Страница 39: ...100 900W Internal Batteries Only 105 52 30 20 15 12 10 8 6 5 Internal 1 E4804 12 585 292 180 120 90 72 66 53 41 35 Internal 2 E4804 12 1065 532 330 220 165 132 122 98 76 65 Internal 3 E4804 12 1545 77...

Страница 40: ...Voltage 120 120 Input Current 12 0 Amps 12 0 Amps Input Voltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 8 35 7 5 Amps 8 35 7 5 Amps Outpu...

Страница 41: ...2 E4804 12 1065 532 330 220 165 132 122 98 76 65 Internal 3 E4804 12 1545 772 480 320 240 192 178 143 111 95 Internal 4 E4804 12 2025 1012 630 420 315 252 234 188 146 125 Internal 5 E4804 12 2505 125...

Страница 42: ...iciency w o Charger 91 Input Voltage 230 Input Current 6 25 Amps Output Voltage 230 Output Current VA Watts 4 35 3 90 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On M...

Страница 43: ...540W 70 630W 80 720W 90 810W 100 900W Internal Batteries Only 105 52 30 20 15 12 10 8 6 5 Internal 1 E4804 12 585 292 180 120 90 72 66 53 41 35 Internal 2 E4804 12 1065 532 330 220 165 132 122 98 76 6...

Страница 44: ...Efficiency w o Charger 91 Input Voltage 230 Input Current 6 25 Amps Output Voltage 230 Output Current VA Watts 4 35 3 90 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation...

Страница 45: ...80 120 90 72 66 53 41 35 Internal 2 E4804 12 1065 532 330 220 165 132 122 98 76 65 Internal 3 E4804 12 1545 772 480 320 240 192 178 143 111 95 Internal 4 E4804 12 2025 1012 630 420 315 252 234 188 146...

Страница 46: ...tery 96 to 144 Volts 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 120 Output Current VA Watts 12 0 10 8 Amps 12 0 10 8 Amps 12 0 10 8 Amps Output Regulation On Mains 10 10 10 Output Regulati...

Страница 47: ...Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48 8 46 5 Internal 3 E4804 12 1260 473 290 192 159 141 95 82...

Страница 48: ...ttery 96 to 144 Volts 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 120 Output Current VA Watts 12 0 10 8 Amps 12 0 10 8 Amps 12 0 10 8 Amps Output Regulation On Mains 10 10 10 Output Regulat...

Страница 49: ...s Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48 8 46 5 Internal 3 E4804 12 1260 473 290 192 159 141 95 8...

Страница 50: ...ltage Range w o Using Battery 96 to 144 Volts 96 to 144 Volts Output Voltage 120 120 Output Current VA Watts 12 0 10 8 Amps 12 0 10 8 Amps Output Regulation On Mains 10 10 Output Regulation On Battery...

Страница 51: ...96 65 56 48 8 46 5 Internal 3 E4804 12 1260 473 290 192 159 141 95 82 71 8 68 5 Internal 4 E4804 12 1650 618 380 252 209 186 125 108 94 8 90 5 Internal 5 E4804 12 2040 763 470 312 259 231 155 134 117...

Страница 52: ...w o Charger 91 Input Voltage 230 Input Current 8 54 Amps Output Voltage 230 Output Current VA Watts 6 30 5 65 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On Mains 10...

Страница 53: ...nternal Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48 8 46 5 Internal 3 E4804 12 1260 473 290...

Страница 54: ...ncy w o Charger 91 Input Voltage 230 Input Current 8 54 Amps Output Voltage 230 Output Current VA Watts 6 30 5 65 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On Mains...

Страница 55: ...7W 80 1036W 90 1166W 100 1296W Internal Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 132 109 96 65 56 48 8 46 5 I...

Страница 56: ...ge 120 Input Current 24 0 Amps Output Voltage 120 Output Current VA Watts 18 5 16 5 Amps Input Voltage Range w o Using Battery 96 to 144 Volts Output Regulation On Mains 10 Output Regulation On Batter...

Страница 57: ...9 5 Internal 3 E4804 12 653 315 195 139 98 76 5 53 44 32 5 27 Internal 4 E4804 12 839 405 250 179 126 98 5 68 56 5 41 5 34 5 Internal 5 E4804 12 1025 495 305 219 154 120 5 83 69 50 5 42 Internal 6 E48...

Страница 58: ...e 230 Input Current 16 0 Amps Output Voltage 230 Output Current VA Watts 9 55 8 60 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On Mains 10 Output Regulation On Batter...

Страница 59: ...225 140 99 70 54 5 38 31 5 23 5 19 5 Internal 3 E4804 12 653 315 195 139 98 76 5 53 44 32 5 27 Internal 4 E4804 12 839 405 250 179 126 98 5 68 56 5 41 5 34 5 Internal 5 E4804 12 1025 495 305 219 154...

Страница 60: ...nd 115 230 and 115 Output Current VA Watts 12 0 11 5 and 24 0 21 6 Amps 12 0 11 5 and 24 0 21 6 Amps Input Voltage Range w o Using Battery 166 to 250 Volts 184 to 276 Volts Output Regulation On Mains...

Страница 61: ...104 70 50 41 26 16 8 15 2 12 Internal 3 E4804 12 539 418 146 98 70 58 36 22 8 21 2 16 5 Internal 4 E4804 12 689 538 188 126 90 75 46 28 8 27 2 21 Internal 5 E4804 12 839 658 230 154 110 92 56 34 8 33...

Страница 62: ...oltage 230 Input Current 16 0 Amps Output Voltage 230 Output Current VA Watts 12 0 10 8 Amps Input Voltage Range w o Using Battery 185 to 276 Volts Output Regulation On Mains 10 Output Regulation On B...

Страница 63: ...12 389 298 104 70 50 41 26 16 8 15 2 12 Internal 3 E4804 12 539 418 146 98 70 58 36 22 8 21 2 16 5 Internal 4 E4804 12 689 538 188 126 90 75 46 28 8 27 2 21 Internal 5 E4804 12 839 658 230 154 110 92...

Страница 64: ...tage 120 120 Output Current VA Watts 15 0 13 5 Amps 15 0 13 5 Amps Input Voltage Range w o Using Bat tery 96 to 144 Volts 96 to 144 Volts Output Regulation On Mains 10 10 Output Regulation On Battery...

Страница 65: ...115 96 72 54 43 35 5 29 5 Internal 3 E4804 12 975 420 263 160 136 101 76 60 49 5 41 5 Internal 4 E4804 12 1265 540 338 205 176 130 98 77 63 5 53 5 Internal 5 E4804 12 1555 660 413 250 216 159 120 94 7...

Страница 66: ...egan IL 60085 1 800 369 7179 P 847 596 7000 F 847 596 7100 Canada Address 700 Finley Avenue Unit 3 Ajax Ontario L1S 3Z2 P 905 239 9284 Europe Asia Address Unit 5 Birch Kembrey Park Swindon Wilts SN2 8...

Отзывы: