ELECTRICAL
Table 3. Allowable Ampacities of Insulated Conductors
1
Size
Temperature Rating of Conductor
Size
60 °C
(140 °F)
75 °C
(167 °F)
85 °C
(185 °F)
90 °C
(194 °F)
60 °C
(140 °F)
75 °C
(167 °F)
85 °C
(185 °F)
90 °C
(194 °F)
AWG
MCM
Types
RUW,
TTW,
and UF
Types
FEPW,
RH,
RHW,
RUH,
THW,
THWN,
XHHW,
USE,
and
ZW
Types
V, and
MI
Types
TA, TBS,
SA,
AVB,
SIS,
FEP
2
,
FEPB
2
,
RHH
2
,
THHN
2
,
and
XHHW
2, 3
Types
RUW,
TTW,
and UF
Types
RH,
RHW,
RUH,
THW,
THWN,
XHHW,
and
USE
Types
V, and
MI
Types
TA,
TBS,
SA,
AVB,
SIS,
RHH
2
,
THHN
2
,
and
XHHW
2, 3
AWG
MCM
Copper
Aluminum or Copper-Clad Aluminum
18
....
....
....
21
....
....
....
....
....
16
....
....
22
22
....
....
....
....
....
14
15
15
25
25
....
....
....
....
....
12
20
20
30
30
15
15
25
25
12
10
30
30
40
40
25
25
30
30
10
8
40
45
50
50
30
40
40
40
8
6
55
65
70
70
40
50
55
55
6
4
70
85
90
90
55
65
70
70
4
3
80
100
105
105
65
75
80
80
3
2
115
120
120
75
90
95
95
2
1
130
140
140
100
110
110
1
0
150
155
155
120
125
125
0
00
175
185
185
135
145
145
00
000
200
210
210
155
165
165
000
0000
230
235
285
180
185
185
0000
250
255
270
270
205
215
215
250
300
285
300
300
230
240
240
300
350
310
325
325
250
260
260
350
400
335
360
360
270
290
290
400
500
380
405
405
310
330
330
500
Correction Factors
Ambient
Temp °C
For ambient temperatures over 30 °C, multiply the ampacities shown above by the
appropriate correction factor to determine the maximum allowable load current.
Ambient
Temp °F
1.
Not more than three conductors in raceway, cable, or earth (directly buried), based on ambient temperature of 30°C (86°F)
2.
+The load current rating and the overcurrent protection for these conductors shall not exceed 15 amperes for 14 AWG. 20
amperes for 12 AWG and 30 amperes for 10 AWG copper; or 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum
and copper-clad aluminum.
3.
*For dry locations only. See 75°C column for wet locations.
GENERAL
The installation must conform with these instructions and the
local code authority having jurisdiction and the requirements of
the power company. In the absence of local codes, the installation
must comply with the current editions of the National Electrical
Code, NFPA 70 or the Canadian Electrical Code CSA C22.1.
An electrical ground is required to reduce risk of electrical shock
or possible electrocution. The water heater should be connected
to a separate grounded branch circuit with over-current protection
and disconnect switch. The water heater should be grounded in
accordance with national and local codes.
Voltage applied to the heater should not vary more than +5%
to -10% of the model and rating plate marking for satisfactory
operation.
Содержание 120 series
Страница 8: ...8 FEATURES AND COMPONENTS Figure 3 Electronic Control Models...
Страница 9: ...9 FEATURES AND COMPONENTS Figure 4 Surface Mount Control Models...
Страница 15: ...15 WIRING DIAGRAMS Figure 8 CCB Central Control Board Control Circuit Diagram Electronic Control Models...
Страница 50: ...50 NOTES...
Страница 51: ...51 NOTES...
Страница 52: ...52 www hotwater com Copyright 2017 A O Smith Corporation All rights reserved...