American Water Heater 120 series Скачать руководство пользователя страница 24

24

TEMPERATURES MENU

OPERATING SET POINT 

User adjustable setting 90°F to 190°F range; factory default is 

120°F. When the water temperature sensed by the control system 

from the immersion Temperature Probe reaches the Operating 

Set Point the control system will end the heating cycle. A call for 

heat will be activated again when the water temperature drops 

below the Operating Set Point minus the 1st Differential Setting.
Example: Operating Set Point is 120°F, the 1st Differential Setting 

is 2°F (factory default). A call for heat will be activated when the 

sensed water temperature drops to 118°F.

Table 7. Operating States

State

Description

Standby

The water heater is not in an active heating cycle. This usually indicates the temperature in the tank has 

reached the Operating Set Point and the control system has terminated the heating cycle.

Heating

The control system is in the Heating Mode. At least one bank of heating elements has been energized.

Alert

The control system has detected/declared an Alert Condition. The controls system will continue heating 

operation. However, a Qualified Service Agent should be contacted to check/service the water heater.

Fault

The control system has detected/declared a Fault Condition. The control system will discontinue heating 

operation and “lock out.” Power to the water heater must be cycled off and on to reset the control system. 

Note; cycling power will not reset the control system until the condition that caused the fault has been cor

-

rected.

Table 8. Control System Menus

Menus

Description

Temperatures

Most commonly accessed menu. Operating Set Point, Differential settings, Tank Temperature and Tank 

Probe Offset are located in this menu.

Heater Status

Current Operating State/Mode (heating/standby etc) and status (open/closed - on/off - yes/no) of moni

-

tored water heater functions and components are displayed in this menu.

Economy Mode Setup

Seven day 24 hour time clock with temperature set back capability to reduce operating costs during unoc

-

cupied or reduced demand periods.

Alarm Output

Setup

The control system’s CCB (Central Control Board) features on board SPDT (single pole double throw) re

-

lay contacts for building EMS (Energy Management System) notification of operational conditions such as 

Fault Conditions and heating mode status. This menu features a list of user definable conditions for relay 

activation.

Display Settings

Temperature units (°F or °C), appearance (brightness contrast) and backlight delay user adjustable set

-

tings are located in this menu.

Heater Information

Elapsed time of operation, total heating cycle time, heating cycle count, heating element bank(s) cycle 

count and heating bank on time along with UIM and CCB software revisions can be viewed in this menu.

Current Fault/Alert

Displays any current Alert or Fault messages.

Fault History

Retains 9 event history of Fault/Alert messages with time stamp. The Fault History is useful when dealing 

with intermittent operational problems or when the customer has reset the control system prior to a service  

agent’s arrival.

Fault Occurrence

Running total of all Fault and Alert Conditions that have occurred are displayed in this menu. Can help 

determine potential root cause(s) of related operational problems.

Restore Factory 

Defaults

This control system feature allows the user to restore control system user settings to their factory default 

settings. Alarm Output Setup and Display Settings menu items ARE NOT changed when factory defaults 

restored.

Help Menu

Accessible by pressing the corresponding Operational Button from most menus and screen displays. This 

menu provides access to instructions and explanations for user settings, Operating States, Status Icons, 

manufacturer’s web address, technical support phone number and service agent contact information.

Содержание 120 series

Страница 1: ...CE MAINTENANCE LIMITED WARRANTY Instruction Manual PRINTED 0917 OPTIONAL Thank you for buying this energy efficient water heater We appreciate your confidence in our products PLACE THESE INSTRUCTIONS...

Страница 2: ...situation which if not avoided could result in minor or moderate injury CAUTION CAUTION indicates a potentially hazardous situation which if not avoided could result in minor or moderate injury All sa...

Страница 3: ...be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater HYDROGEN GAS FLAMMABLE Hydrogen gas can be produced in a hot water system served by thi...

Страница 4: ...ING DIAGRAMS 41 PIPING DIAGRAMS 47 MANIFOLD KITS 49 NOTES 50 NOTES 51 SAFE INSTALLATION USE AND SERVICE 2 GENERAL SAFETY INFORMATION 3 Precautions 3 Hydrogen Gas Flammable 3 INTRODUCTION 5 Preparing f...

Страница 5: ...ts of the heater are identified on pages 7 8 The model and rating plate on page 6 interprets certain markings into useful information Both of these references should be used to identify the heater its...

Страница 6: ...51 47 44 18 61 434 246 184 148 123 105 92 82 74 67 61 57 53 24 81 912 328 246 197 164 140 123 109 98 89 82 76 70 27 92 151 369 276 221 184 158 138 123 111 101 92 85 79 30 102 390 410 307 246 205 176...

Страница 7: ...by Underwriters Laboratories Inc MODEL AND RATING LISTED 22U1 No OF WATTS PHASE VOLTS AC ELEMENTS EACH RATED MEASURED WATTS COMMERCIAL STORAGE TANK WATER HEATER MODEL NUMBER SERIAL NUMBER ITEM ID PART...

Страница 8: ...8 FEATURES AND COMPONENTS Figure 3 Electronic Control Models...

Страница 9: ...9 FEATURES AND COMPONENTS Figure 4 Surface Mount Control Models...

Страница 10: ...er should be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the heater or to lower floors of the structure Close to the point of major ho...

Страница 11: ...imum water temperature at the hot water tap then you must take special precautions In addition to using the lowest possible temperature setting that satisfies your hot water needs a means such as a MI...

Страница 12: ...ly operated at least once a year Caution should be taken to ensure that 1 no one is in front of or around the outlet of the temperature pressure relief valve discharge line and 2 the water manually di...

Страница 13: ...r 30 C multiply the ampacities shown above by the appropriate correction factor to determine the maximum allowable load current Ambient Temp F 1 Not more than three conductors in raceway cable or eart...

Страница 14: ...volt rating Do not substitute fuses of a different rating Sequence of Operation 1 When the control is powered the UIM should display model information water temperature Operating Set Point heating st...

Страница 15: ...15 WIRING DIAGRAMS Figure 8 CCB Central Control Board Control Circuit Diagram Electronic Control Models...

Страница 16: ...he heater circuits and includes wiring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C Fus...

Страница 17: ...es to terminal L2 with red wires 4 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connection to a single phase electrical service it may be connecte...

Страница 18: ...s the heater circuits and includes wiring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C...

Страница 19: ...Disconnect all red wires from terminal L3 4 Connect all red wires to terminal L2 with yellow wires 5 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for...

Страница 20: ...odels only 4 Turn on the electrical disconnect switch 5 Observe the operation of the electrical components during the first heating cycle Use care as the electrical circuits are energized 6 Close the...

Страница 21: ...ystem THERMOSTAT CONTROLS The water heaters covered in this instruction manual are equipped with adjustable thermostat controls to control water temperature Hot water temperatures required for automat...

Страница 22: ...me periods Helps reduce operating costs during unoccupied or peak demand periods Linear Sequencing Banks of heating elements 3 elements per bank are energized according to adjustable 1 to 20 different...

Страница 23: ...is a call for heat present and the control system has initiated heating operation Heating elements icon for a water heater equipped with 1 Bank of heating elements Each circle repre sents one heating...

Страница 24: ...moni tored water heater functions and components are displayed in this menu Economy Mode Setup Seven day 24 hour time clock with temperature set back capability to reduce operating costs during unoc c...

Страница 25: ...ision of temperature control in the storage tank and at points of use This feature can also be used to compensate for building recirculation loops hot water returning to the storage tank that may caus...

Страница 26: ...relay coil to either circuit ELEMENT BANK ON Displays the on off status of each Bank of heating elements Yes On No Off ALARM CONDITION Displays the status of the user definable Alarm Output function...

Страница 27: ...underneath MENU to enter the Main Menu Notice how the text above the Operational Buttons on the display changes as you navigate through the various menus and screens Use the Up Down buttons to select...

Страница 28: ...changes to ACCEPT CANCEL when the adjustment mode is activated and how the current setting is outlined rather than highlighted in black Press the Operational Button underneath ACCEPT to enter and con...

Страница 29: ...the Up Down and CHANGE buttons to enter the Mon sub menu Use the Up Down buttons to select highlight in black the Normal Operation Between setting Press the Operational Button underneath SELECT to cha...

Страница 30: ...en current tank temperature drops below programmable Alarm SP Fault or Alert Used for external notification whenever a Fault or Alert condition is active Fault Used for notification whenever a Fault c...

Страница 31: ...splays non adjustable operational information The control system records and stores the last 9 Fault and Alert messages in chronological order in this menu The most recent will be at the top of the li...

Страница 32: ...ry default settings have been restored Press the Operational Button underneath BACK to exit the Restore Factory Defaults menu GENERAL Periodically the drain valve should be opened and the water allowe...

Страница 33: ...om water system Check for any leaks and immediately correct any if found 7 Restart the water heater as directed in this manual See the Repair Parts Illustration for anode rod location FLUSHING THE WAT...

Страница 34: ...eans Lime scale dissolvents will not remove these types of scale which are occasionally encountered Call the toll free phone number on the back cover of this Instruction Manual to purchase UN LIME and...

Страница 35: ...are normal however the tank bottom and elements should be cleaned See the Maintenance section of this manual 2 Some of the electrical components of the water heater make sounds which are normal Conta...

Страница 36: ...ll element with new gasket Condensation and dripping may appear on pipes when inlet water temperature is low Pipe fitting may be leaking All water which appears at the heater bottom or on the surround...

Страница 37: ...ELECTRIC 1 UNIT LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNI...

Страница 38: ...hermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCUL...

Страница 39: ...g thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE C...

Страница 40: ...LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING...

Страница 41: ...5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERA...

Страница 42: ...et 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 2 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TE...

Страница 43: ...SURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING...

Страница 44: ...the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL...

Страница 45: ...an the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN...

Страница 46: ...RE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER...

Страница 47: ...ntrol COMMERCIAL ELECTRIC 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERA...

Страница 48: ...Control COMMERCIAL ELECTRIC 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TE...

Страница 49: ...ze 1 1 2 Table 15 Manifold Kits with Three Heaters Tank Capacity Gallons Part Number H W D A 52 100109232 66 1 4 91 3 4 27 1 4 13 1 4 80 100109232 70 1 2 95 1 4 31 1 4 9 3 4 120 100109232 73 1 4 99 1...

Страница 50: ...50 NOTES...

Страница 51: ...51 NOTES...

Страница 52: ...52 www hotwater com Copyright 2017 A O Smith Corporation All rights reserved...

Отзывы: