Service Facts

IMPORTANT — This document contains a wiring diagram, a parts list, and service information. This is customer property and 

is to remain with this unit. Please return to service information pack upon completion of work.

© 2016 Trane

NOTICE:  The manufacturer has a policy of continuous product and product data  improvement 

and it reserves the right to change design and specifications without notice.

WARNING

!

THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS 

POSSESSING ADEQUATE BACKGROUNDS OF ELECTRICAL AND 

MECHANICAL  

EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR 

CONDITIONING PRODUCT MAY RESULT IN PERSONAL INJURY AND 

OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT 

BE RESPONSIBLE FOR THE INTERPRETATION OF THIS INFORMATION, 

NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.

CAUTION

!

RECONNECT ALL GROUNDING DEVICES.

ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING 

ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING 

WIRES, SCREWS, STRAPS, CLIPS, NUTS OR WASHERS USED 

TO COMPLETE A PATH TO GROUND ARE REMOVED FOR 

SERVICE, THEY MUST BE RETURNED TO THEIR  ORIGINAL 

POSITION AND PROPERLY FASTENED.

WARNING:

 

HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 

  

CAPACITORS BEFORE SERVICING

CAUTION

!

UNIT CONTAINS R-410A 

REFRIGERANT!

R-410A OPERATING PRESSURE EXCEEDS THE 
LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS 
REQUIRED. FAILURE TO USE PROPER SERVICE 

SERVICE

USE ONLY R-410A REFRIGERANT AND

APPROVED POE COMPRESSOR OIL.

PRODUCT SPECIFICATIONS

 OUTDOOR UNIT 

12 

 

POWER CONNS. — V/PH/HZ 

3

 MIN. BRCH. CIR. AMPACITY

 BR CIR PROT RTG – MAX. (AMPS)
 

COMPRESSOR

 NO. USED - NO. SPEEDS

 VOLTS/PH/HZ

 R.L. AMPS 

7

 - L.R. AMPS

 FACTORY INSTALLED

  START COMPONENTS 

8

  INSUL/SOUND BLANKET

  COMPRESSOR HEAT
 

OUTDOOR FAN

 DIA. (IN.) - NO. USED

 TYPE DRIVE - NO. SPEEDS

 CFM @ 0.0 IN. W.G. 

4

 NO. MOTORS - HP

 MOTOR SPEED R.P.M.

 VOLTS/PH/HZ

 F.L. AMPS
 

OUTDOOR COIL — TYPE

 ROWS - F.P.I.

 FACE AREA (SQ. FT.)

 TUBE SIZE (IN.)
 

REFRIGERANT

 LBS — R-410A (O.D. UNIT) 

5

 FACTORY SUPPLIED

 LINE SIZE - IN. O.D. GAS 

6

 LINE SIZE - IN. O.D. LIQ. 

6

 

CHARGING SPECIFICATION 

 SUBCOOLING
 

DIMENSIONS

 CRATED (IN.)
 

WEIGHT

 SHIPPING (LBS.)

 NET (LBS.)

4TWA3B-SF3-3F-EN

Split System  

Cooling

4TWA3036B3000A, 4TWA3042B3000A, 
4TWA3048B3000B, 4TWA3060B3000A

02/17

4TWA3060B3000A

208/230/3/60

20

35

SCROLL

1 - 1

208/230/3/60

15.6 - 110

NO

NO

YES

PROPELLER

27.6 - 1

DIRECT - 1

4760

1 - 1/5

850

200/230/1/60

.93

SPINE FIN™

1 - 24

27.86

3/8

8 LBS., 14 OZ.

YES

7/8

3/8

8°F

H  X  W  X  D

46.4 x 35.1 x 38.7

280

244

4TWA3042B3000A

208/230/3/60

18

30

SCROLL

1 - 1

208/230/3/60

13.6 - 83

NO

NO

YES

PROPELLER

27.6 - 1

DIRECT - 1

4395

1 - 1/5

850

200/230/1/60

.93

SPINE FIN™

1 - 24

21.99

3/8

7 LBS., 7 OZ.

YES

3/4

3/8

8°F

H  X  W   X  D

38.4 x 35.1 x 38.7

248

214

4TWA3036B3000A

208/230/3/60

14

20

SCROLL

1 - 1

208/230/3/60

10.4 - 73

NO

NO

YES

PROPELLER

27.6 - 1

DIRECT - 1

4385

1 - 1/5

850

200/230/1/60

.93

SPINE FIN™

1 - 24

21.99

3/8

7 LBS., 14 OZ.

YES

3/4

3/8

10°F

H  X  W   X  D

38.4 x 35.1 x 38.7

228

197

4TWA3048B3000B

208/230/3/60

18

30

SCROLL

1 - 1

208/230/3/60

13.7 - 83

NO

NO

YES

PROPELLER

27.6 - 1

DIRECT - 1

4400

1 - 1/6

835

200/230/1/60

1.30

SPINE FIN™

1 - 24

27.86

3/8

8 LBS., 10 OZ.

YES

7/8

3/8

10°F

H  X  W   X  D

46.4 x 35.1 x 38.7

279

243

1

  Certified in accordance with the Air-Source Unitary Air-conditioner 

Equipment certification program, which is based on AHRI standard 

210/240.

2

  Rated in accordance with AHRI standard 270.

3

  Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit 

breakers or fuses.

4

  Standard Air — Dry Coil — Outdoor

5

  This value approximate. For more precise value see unit nameplate.

6

  Max. linear length 60 ft.; Max. lift - Suction 60 ft.; Max lift - Liquid 60 ft.  

For greater length consult refrigerant piping software Pub. No. 32-3312-

0* (* denotes latest revision).

7

  This value shown for compressor RLA on the unit nameplate and on this 

specification sheet is used to compute minimum branch circuit ampacity 

and max. fuse size. The value shown is the branch circuit selection cur-

rent.

8

  No means no start components. Yes means quick start kit components. 

PTC means positive temperature coefficient starter.

CONTAINS REFRIGERANT!

SYSTEM CONTAINS OIL AND REFRIGERANT 
UNDER 

HIGH PRESSURE. RECOVER REFRIGERANT TO 

RELIEVE PRESSURE BEFORE OPENING SYSTEM.

CAUTION

!

HOT SURFACE!

DO NOT TOUCH TOP OF 

CAUTION

!

TUBING INFORMATION

LINE TYPE

REFRIGERANT TO ADD AT SPECIFIED 

ADDITIONAL LENGTH

Suction  Liquid

20 ft

30 ft

40 ft

50 ft

60 ft

3/4"

3/8"

3 oz

9 oz

15 oz

21 oz

27 oz

7/8"

3/8"

3 oz

9 oz

16 oz

22 oz

28 oz

Содержание 4TWA3036B3000A

Страница 1: ...tem Cooling 4TWA3036B3000A 4TWA3042B3000A 4TWA3048B3000B 4TWA3060B3000A 02 17 4TWA3060B3000A 208 230 3 60 20 35 SCROLL 1 1 208 230 3 60 15 6 110 NO NO YES PROPELLER 27 6 1 DIRECT 1 4760 1 1 5 850 200...

Страница 2: ...Line Temperature and Refrigerant Pressure at service valves 5 Determine total refrigerant line length and height lift if indoor section is above the condenser Use the Subcool Charging Chart Correctio...

Страница 3: ...T Refer to Service Facts or Installer s Guide for charging method LIQUID TEMP F DESIGN SUBCOOLING F LIQUID GAGE PRESSURE PSI From Dwg D154557P01 Rev 2 1 The Subcool Charging Method in cooling is not r...

Страница 4: ...one minute Does Liquid pressure decrease and suction pressure increase YES Replace the TXV TXV is OK Measure superheat on suction line at TXV sensing bulb Is superheat over 6 F and under 20 F NO YES...

Страница 5: ...to Wiring Diagram to determine if a single pole or double pole contactor is used Check for open IOL Internal Overload Check resistance of C to S and C to R Does the resistance check show an open circ...

Страница 6: ...ture of 70 when the ambient tem perature is below 30 see table at left Defrost Board Detail Defrost Termination Temperatures Outdoor Temperature Termination Temperature As Shipped 22 F 47 F 10 F 22 F...

Страница 7: ...N PRESSURE PSIG 125 130 135 140 145 150 155 160 165 170 200 250 300 350 400 450 500 40 60 80 100 120 1 1 3 3 5 4 2 2 INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM 71 67 63 AND 59 DEG F INDOOR ENTERING...

Страница 8: ...5 375 425 475 5 5 15 25 35 45 55 65 INDOOR ENTERING DRY BULB CURVES TOP TO BOTTOM 80 70 AND 60 DEG F INDOOR ENTERING DRY BULB CURVESTOP TO BOTTOM 80 70 AND 60 DEG F PRESSURE CURVES FOR 4TWA3048B4 TAM4...

Отзывы: