background image

Install Surge Arrester & Surge Detector

Required Tools

 

Anti-static wrist strap

 

Small Phillips (#2) screwdriver

 

Voltmeter

 

Crimper

 

10 AWG wire - stranded or solid; insulated or bare

1

 

Connect 

surge arrester

 to rectifier or device according to the instructions included with the arrester 

(

Surge Arrester - High Energy Installation Quick Reference Guide

, part number 122186-000).  

Complete 

only Step 1.

 NOTE:

  If the surge arrester was already installed, disconnect the 

surge arrester

’s white ground wire from 

its ground location. 

2

 

Cut off the spade connector from the end of the 

surge arrester

’s white wire.

3

  Thread the 

surge arrester

’s

 

white wire through the hole (marked 

Pulse

)

 on 

the 

Surge Detector

’s current transformer.

4

 

Connect a spade connector (included in kit) to the end of the white wire.

5

 

Connect the white wire to same ground location as before, which should be the 

same point as the Bullhorn unit’s ground.

6

 

Wire and connect the 

Surge Detector

 to the Bullhorn remote monitoring unit’s accumulator channel.

Install SurgeFuse

2

1

  Place the 

SurgeFuse

 between your facility and your Bullhorn remote monitoring unit (RMU). 

2

  Connect an output from the facility to either 

Ch A

 or 

Ch B

 on the 

SurgeFuse

OR 

move the connector currently connected to a channel on the RMU to either 

Ch A

 or 

Ch B

Repeat for a second output if necessary.

3

  Wire and connect the corresponding output on the 

SurgeFuse

 (labeled 

RMU

)

to the input channel on the

 

Bullhorn RMU that is used for that facility 

output. Repeat for a second output if necessary. 

4

  Connect the 

SurgeFuse

’s green ground wire to the Bullhorn RMU’s ground 

screw inside the unit’s enclosure.

IMPORTANT: 

 Refer to the diagram on the back of this guide for more 

information regarding wiring and the relationships between the devices.

Surge Detector

WARNING:

 

If wires are to be buried or covered, use conduit to protect the wires.

1

Installing the Equipment

WARNING

:

 

To prevent electrostatic discharge (ESD) damage when handling electronic equipment, always wear an 

anti-static wrist strap attached to an unpainted, grounded metal object. Ensure the wrist strap has maximum contact 

with bare skin.

 

WARNING

:

 

Before beginning any wiring, disconnect all equipment from hazardous voltages.

© 2018 American Innovations, Ltd. 

The SurgeProtect Kit includes an HE surge arrester, a SurgeFuse, and a Surge Detector. The surge arrester and SurgeFuse 

work together to protect remote monitoring units and devices from lightning strikes and other electrical surges. The 

Surge Detector keeps track of surge events and related information, which is then transmitted to Bullhorn Web.

SurgeFuse

(Continued on back.)

SurgeProtect Kit Installation

Quick Reference Guide

Part No. 122238-000, Rev. 0

1 of 2

Отзывы: