American Dynamics RCSN422 Скачать руководство пользователя страница 4

 

SENSORNET TO RS-422 CODE CONVERTER 

8000-2593-01, REV. C 

INSTALLATION GUIDE 

4 of 7

 

Troubleshooting 

The converter's front-panel LEDs indicate when 
activity occurs during operation. They also identify 
many errors that could occur: 

422 LED on 
steadily  

ROM checksum or RAM 
read/write failure. Reload 
software from host. 

(noise) LED 

flashes randomly  

Indicates SensorNet 
transmission errors. 

485 LED off 

No SensorNet protocol detected. 

 LED Off 

No power. 

µP LED flashes 
rapidly  

Code converter in loopback test. 

 

Addendums 

Addendum A:

 

Performing a

 

SensorNet Ping Test on a 

Dome Camera

 

To conduct a ping test from the controller to a 
dome, select the dome camera and run the test 
(described in the appropriate operator manual). 

Note: 

-  Address selected at the controller determines 

the dome camera tested. 

-  Dome address switch settings must be correct. 
-  The code converter responds to pings if the 

dome is responding. 

-  If the code converter is selected, only the 

communication line from the controller to the 
converter is tested. 

-  For how to get dome information and to conduct 

the ping test from the controller, refer to 
ADTT16E (8200-0306-02) and VM16 (8000-
2653-01) operation instructions. For just the 
ping test, refer to MegaPower LT operation 
instructions (MP-LTHB-1). 

Note:

 If a controller requests device information 

from a camera having the same address as the 
converter, the controller receives configuration 
information from the converter instead of the dome. 

Addendum B: 

Performing an RS-422 Line Test

 

For each RS-422 port: Press and hold the port’s 
line status test switch and view the adjacent LED. 
The LED lights as follows: 

Constant green, 
Blinking red 

RS-422 line correctly wired. 

Constant green, 
No red 

"Data In" – shorted to ground. 

Constant red, 
Blinking green  

"Data In" + and – wires 
reversed. 

Blinking red, 
Green off 

"Data In" + shorted to ground. 

Both LEDs off 

"Data In" + and – wires shorted 
or open. 

Addendum C: 

Resetting the Code Converter

 

If communications cease, press the reset switch on 
the front panel using a paper clip. If that fails, try 
recycling power. 

Addendum D: 

Performing an

 

RS-422 Loopback Test

 

1.  Disconnect data lines from all seven RS-422 

connectors. 

2.  Wire each connector’s pins as follows: 

Pin 1 white wire (RX+) loops to Pin 3 (TX+) 
Pin 2 gray wire (RX–) loops to Pin 4 (TX–) 

3.  Set the code converter to address 00. 

4.  Press the RS-422 line test switch to the right of 

the port. 

5.  If the LED adjacent top the port lights, that port 

is working. If the LED remains off, the port is not 
working. 

6.  Repeat steps 4 and 5 for the next port. 
 

Содержание RCSN422

Страница 1: ...tallation The converter can be placed on a tabletop or installed in a rack under a shelf or on a wall Parts Supplied Install Kit 0351 1635 01 which includes Mounting Bracket 2 Screw PHP M3x8 4 Connect...

Страница 2: ...First blink indicates a successful ROM check second blink indicates a successful RAM check LED illuminates continuously when either check fails stopping the test Remains illuminated during program loa...

Страница 3: ...EU ist es f r den Betrieb durch eine begrenzte Stromquelle vorgesehen Eine begrenzte Stromquelle ist eine zertifizierte SELV Quelle Schutzkleinspannung bei inh renter Begrenzung mit einem maximalen A...

Страница 4: ...instructions For just the ping test refer to MegaPower LT operation instructions MP LTHB 1 Note If a controller requests device information from a camera having the same address as the converter the c...

Страница 5: ...L 860 AP J Box To MiniDome To Unicard SpeedDome To Optima To Optima LT To SpeedDome Ultra Pigtail To SpeedDome Ultra I O J1 10 J5 P3 P1 P7 Pin 1 TX Pin 1 RX Pin 7 RX Pin 1 RX Pin 1 RX Pin 6 RX Pin 1 R...

Страница 6: ...Dome Ultra Pigtail To SpeedDome Ultra I O J1 10 J5 P3 P1 P7 Pin 1 TX Pin 1 RX Pin 7 RX Pin 1 RX Pin 1 RX Pin 6 RX Pin 1 RX Pin 2 TX Pin 2 RX Pin 6 RX Pin 2 RX Pin 2 RX Pin 7 RX Pin 2 RX Pin 3 AC Pin 3...

Страница 7: ...y it to c program files AD_Utilities Note This file must be F2814 0102 or higher 3 Set the code converter to address 32 4 Launch the ADCASNET utility and click Load Utility 5 Click the Scan Network ic...

Отзывы: