22
American Dryer Corp.
113247 - 3
ADEH-75 Electric Models Only
All electrically heated dryers must be connected to the electric
service shown on the dryer’s data label. The connecting
wires must be properly sized to handle the rated current.
* Customer must contact factory to special order 3-wire systems.
8/15/07
ADEH-170 Electric Models Only
Available upon request. Contact the factory.
Grounding
A ground (earth) connection must be provided and installed
in accordance with state and local codes. In the absence of
these codes, grounding must conform to applicable
requirements of the National Electrical Code ANSI/NFPA NO.
70-LATEST EDITION, or in Canada, the installation must
conform to applicable Canada Standards: Canadian Electrical
Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION.
The ground connection may be to a proven earth ground at
the location service panel.
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT
:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When
ordering, specify exact voltage.
When fuses are used they must be dual element, time delay,
current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY.
For others, calculate/verify correct breaker size according
to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
60 kW
380
3ø
4*
—
100
125
416
3ø
4*
—
91
125
480
3ø
3
80
—
100
600
3ø
3
64
—
80
72 kW
208
3ø
3
214
—
300
240
3ø
3
188
—
250
230
3ø
3
—
198
250
380
3ø
3
118
—
150
380
3ø
4*
—
118
150
400
3ø
4*
—
113
150
416
3ø
4*
—
108
150
460
3ø
3
98
—
125
480
3ø
3
94
—
125
575
3ø
3
78
—
100
75.6 kW
440
3ø
3
102
—
150
* Customer must contact factory to special order 3-wire systems.
8/15/07
ADEH-120 Electric Models Only
All electrically heated dryers must be connected to the electric
service shown on the dryer’s data label. The connecting
wires must be properly sized to handle the rated current.
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT
:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When
ordering, specify exact voltage.
When fuses are used they must be dual element, time delay,
current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY.
For others, calculate/verify correct breaker size according
to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
30 kW
208
3ø
3
91
—
125
230
3ø
3
—
83
125
240
3ø
3
79
—
100
380
3ø
3
48
—
60
380
3ø
4*
—
54
70
400
3ø
4*
—
51
70
416
3ø
4*
—
50
70
460
3ø
3
40
—
50
480
3ø
3
39
—
50
575
3ø
3
33
—
50
36 kW
208
3ø
3
108
—
150
230
3ø
3
—
98
125
240
3ø
3
94
—
125
380
3ø
3
58
—
80
380
3ø
4*
—
63
80
400
3ø
4*
—
60
80
416
3ø
4*
—
58
80
460
3ø
3
48
—
60
480
3ø
3
46
—
60