BR735D Extended Eng R1.0 1509

 

-1/7- 

Amdar Ltd.

 

 

 

 

SURGE ANTICIPATING UPS CONTROLLER

 

 

BR735D-UPS 

 

 

 

 
 
The Surge Anticipating UPS Controller, together with the Surge Anticipating Control 
Valve – SACV, are designed to protect pump unit systems by discharging pressure surge waves, 
caused by sharp liquid flow velocity changes at random pump operation stops. Normally, such 
situation is encountered under Utility Power Supply failure, which usually generates undesired 
negative liquid pressure. The UPS senses such conditions and triggers an appropriate response in 
order to energize the SACV which, when being activated, discharges this undesired negative 
liquid pressure. 

 

 

Содержание BERMAD BR735D-UPS

Страница 1: ...o protect pump unit systems by discharging pressure surge waves caused by sharp liquid flow velocity changes at random pump operation stops Normally such situation is encountered under Utility Power S...

Страница 2: ...eginning installation disconnect all electrical power to the equipment Unpacking After unpacking the unit check it for compliance and any damages which may have occurred during shipment This product s...

Страница 3: ...odes of error and warnings please refer to Table 1 This table is also located on the rear side of the partly transparent cover There are two modes of solenoid operation select one using program interf...

Страница 4: ...es they must be protected from being completely or even partially depleted As such at the end of the user defined operation period 6 to 120 sec the electronic circuit disconnects the SACV and also its...

Страница 5: ...tivation time TSOL t SoL on display 6 180 Seconds 60 Seconds Solenoid operation MODE SoL A As on display P1 or P2 P1 Alarm relay operation mode rELY As on display Normal 1 or Reverse 2 Normal Communic...

Страница 6: ...OL 6 180 Seconds Time Delay TD1 OFF or 0 30 Seconds Alarm Relay Changeover Contact Floating Nominal Current 5A 220VAC under resistive load Max Values 5A 30VDC under resistive load Load Current Up to 2...

Страница 7: ...The above data may be changed without prior notice BR735D Extended Eng R1 0 1509 7 7 Amdar Ltd Wiring Diagram...