Motor Connector
Figure R1.2 also shows the location of the Stepper Motor Connector. The mate to this connector is included
with the SD4840EK and is also available from AMCI under the part number MS-4M. It is also available from
Phoenix Contact under their part number 187 80 37.
Front Panel
The front panel of the SD4840EK contains the drive status LED as well as
the two EtherCAT status LED’s.
Status LED
The Status LED is a bi-color red/green LED shows the general status of the
module.
Steady Green:
Module OK
Steady Red:
An Overtemperature Fault or Motor Short Circuit Fault
exists. Note that the SD4840EK will only detect short
circuit faults when the motor current is enabled.
Blinking Green:
Successful write to flash memory. Power must be
cycled to the module before additional commands
can be written to it.
Blinking Red:
Failed write to flash memory. You must cycle power
to the module to clear this fault.
Alternating Red/Green:
There is a communications error between the
main processor and the Ethernet co-proces-
sor within the drive. You must cycle power
to the module to attempt to clear this fault.
EtherCAT Run LED
The green RUN LED indicates the logical state of the device.
Table R1.4 Module RUN LED States
EtherCAT ERR LED
The red ERR LED indicates an error state in the EtherCAT protocol.
Table R1.5 Red ERR LED States
LED State
Description
Off Device in the EtherCAT Init state
Fast Blink (4 Hz) Device in the EtherCAT Pre-Operational (Pre-Op) state
Slow Blink (1 Hz) Device in the EtherCAT Safe-Operational (Safe-Op) state
Steady Green Device in the EtherCAT Operational (Op) state.
Red LED State
Description
Off No errors in device operation
Single blink
200 ms ON / 1 s OFF
Problems with synchronization such as with the Distrib-
uted Clock (DC) PLL.
Double Blink
200 ms Pulses / 1 s between
SYNC manager watchdog timeout. The master has not
updated the output data in the configured time interval. The
Networked Driver has switched to the Safe-OP state.
Slow Blink
(1 Hz)
All other issues, such as cable disconnect. The Networked
Driver has switched to the Safe-OP state.
Figure R1.3 SD4840EK Front Panel
STATUS
RUN ERR
MOTION
SD4840
STEPPER
DRIVER
Содержание SD4840EK
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0S310...
Страница 6: ...TABLE OF CONTENTS SD4840EK User Manual ADVANCED MICRO CONTROLS INC 6 Notes...
Страница 38: ...MOVE PROFILES SD4840EK User Manual ADVANCED MICRO CONTROLS INC 38 Notes...
Страница 48: ...CALCULATING MOVE PROFILES SD4840EK User Manual ADVANCED MICRO CONTROLS INC 48 Notes...
Страница 78: ...COMMAND DATA FORMAT SD4840EK User Manual ADVANCED MICRO CONTROLS INC 78 Notes...
Страница 94: ...INSTALLING THE SD4840EK SD4840EK User Manual ADVANCED MICRO CONTROLS INC 94 Notes...
Страница 104: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...