PressPro Genesis Manual Addendum
The following document contains information that is not contained in the standard PressPro
Genesis manual.
Fault Stop Output
The fault Stop output is typically on. That is, the output will turn off when a fault condition is
detected. The following is the list of conditions that will cause the Fault Output to turn off.
¾
If a fault condition is detected on one of the Die Monitoring inputs. This assumes that the
Die Monitoring input has been configured to use the Fault Stop output.
¾
A fault is detected on the Brake Input
¾
If a Transducer Fault is detected
Additional Configuration Parameters
Eight parameters can be programmed on Configuration Screen 4 of 4. These parameters, along
with their function and default values, are shown in the following tables.
C O N F I G U R E 4 O F 4
C
L
E
A
R F
A
U
L
T
S N
O
V I E W * * P : * * * S P M * * * *
To move from one parameter to the next, move the blinking cursor over the parameter and press
the SELECT key. When the desired parameter is reached, press the ENTER or
¾
arrow key to
move the cursor to the next data field, where the SELECT key is used to select between NO and
YES.
Parameter
Function
Default
Clear Faults
If “YES”, a user with an Operator Level access is allowed to clear
any faults that occur.
NO
Select Tool #
If “YES”, a user with an Operator Level is allowed to change
which program is currently running.
NO
INC / DEC
If “YES”, a user with an Operator Level is allowed to Increment
or Decrement the Limit Switch On/Off setpoints
NO
Clear Counters
If “YES”, a user with an Operator Level access is allowed to clear
the Actual Batch and Total counters. Regardless of the setting,
only a user with Master or Setup level access are allowed to clear
the Tool and Stroke counters.
NO
Brake Monitor
If “YES”, it allows the Brake Monitoring functions to occur. Any
transitions on the Brake Input will be ignored if this parameter is
set to “NO.”
NO
Motion Detect
If “YES”, it allows the Motion Detect operations to occur. Motion
detect errors will not be reported if this parameter is set to “NO.”
NO
Latch Transd Err
If “YES”, the Genesis unit will remain in transducer fault until it is
cleared by the user. If set to “NO” the transducer fault will clear
as soon as the resolver signals become valid.
YES
Count Input 1
If “YES” the batch counter will increase whenever input 1
transitions. If “NO” the batch counter will increase when the
resolver’s position data passes through the zero point.
NO