PressPro Genesis Manual Addendum

The following document contains information that is not contained in the standard PressPro 
Genesis manual.   
 

Fault Stop Output 

 
The fault Stop output is typically on.  That is, the output will turn off when a fault condition is 
detected.  The following is the list of conditions that will cause the Fault Output to turn off.   
 

¾

 

If a fault condition is detected on one of the Die Monitoring inputs.  This assumes that the 
Die Monitoring input has been configured to use the Fault Stop output.    

¾

 

A fault is detected on the Brake Input 

¾

 

If a Transducer Fault is detected   

 

Additional Configuration Parameters 

 
Eight parameters can be programmed on Configuration Screen 4 of 4.   These parameters, along 
with their function and default values, are shown in the following tables.   
 

   C O N F I G U R E  4  O F  4    

R  F 

S       N 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V I E W * *    P : * * *    S P M * * * * 

 
To move from one parameter to the next, move the blinking cursor over the parameter and press 
the SELECT key.  When the desired parameter is reached, press the ENTER or 

¾

 arrow key to 

move the cursor to the next data field, where the SELECT key is used to select between NO and 
YES.   
 

Parameter 

Function 

Default 

Clear Faults 

If “YES”, a user with an Operator Level access is allowed to clear 
any faults that occur.   

NO 

Select Tool # 

If “YES”, a user with an Operator Level is allowed to change 
which program is currently running. 

NO 

INC / DEC 

If “YES”, a user with an Operator Level is allowed to Increment 
or Decrement the Limit Switch On/Off setpoints 

NO 

Clear Counters 

If “YES”, a user with an Operator Level access is allowed to clear 
the Actual Batch and Total counters.  Regardless of the setting, 
only a user with Master or Setup level access are allowed to clear 
the Tool and Stroke counters.      

NO 

Brake Monitor 

If “YES”, it allows the Brake Monitoring functions to occur.  Any 
transitions on the Brake Input will be ignored if this parameter is 
set to “NO.” 

NO 

Motion Detect 

If “YES”, it allows the Motion Detect operations to occur.  Motion 
detect errors will not be reported if this parameter is set to “NO.” 

NO 

Latch Transd Err 

If “YES”, the Genesis unit will remain in transducer fault until it is 
cleared by the user.  If set to “NO” the transducer fault will clear 
as soon as the resolver signals become valid. 

YES 

Count Input 1 

If “YES” the batch counter will increase whenever input 1 
transitions.  If “NO” the batch counter will increase when the 
resolver’s position data passes through the zero point. 

NO 