20 Gear Drive, Plymouth Ind. Park, Terryville, CT 06786
Tel: (860) 585-1254 Fax: (860) 584-1973 http://www.amci.com
EtherNet/IP Protocol
CIP P
OSITION
S
ENSOR
O
BJECT
69
Supported Instance Attributes (continued)
Table R3.3 Supported Instance Attributes
For detailed description of the Attributes, see the CIP definition.
Supported Alarms
The NR60E2 supports the following operational alarm.
Diagnostic Error
This alarm is set when the NR60E2 fails its power up diagnostics. The Position Error alarm is also set to indi-
cate that the position data may be incorrect.
Attributes 16#2D,
Supported Alarms
, 16#2C,
Alarms
, and 16#2E
Alarm Flag
indicate something about the
alarms supported by the NR60E2.
16#2D: Supported Alarms –
Reading this attribute returns a value of 3, indicating that the Position
Error alarm and Diagnostic Error alarms are both used.
16#2C: Alarms –
Reading this attribute will return a value of zero if no alarms have occurred and a
value of three if an alarm has occurred.
16#2E: Alarm Flag –
Reading this attribute will return a value of zero if no alarms have occurred and a
value of one if an alarm has occurred.
Attrib. ID
Access
Name
Data Type
Description
16#19 - 25
Set
Velocity Format
WORD
Format of the velocity attribute:
16#1F04 = pulses/s
16#1F05 = pulses/ms
16#1F07 = steps/min 16#1F0F = RPM
16#29 - 41
Get
Operating Status
BYTE
Encoder diagnostic operating status.
Bit 0 = Value of attribute 16#0C (12)
Bit 1 = Value of attribute 16#0E (14)
16#2A - 42
Get
Physical Resolution
Span
UDINT
Physical resolution of the single-turn
resolver sensor
16#2B - 43
Get
Number of Spans
UINT
Maximum number of revolutions that
could be measured.
16#2C - 44
Get
Alarms
WORD
Indicates a malfunction has occurred.
16#2D - 45
Get
Supported Alarms
WORD
Information about supported alarms
16#2E - 46
Get
Alarm Flag
BOOLEAN
Indicates that an alarm error occurred:
0 = No errors
1 = Alarm Error
16#33 - 51
Get
Offset Value
DINT
The internal position offset that is calcu-
lated after applying the Preset Value
through attribute 13hex (19)
16#64 - 100
Set
Device Type
DINT
The way the device identifies itself:
16#22 (default) = Encoder device
16#00 = Generic device
16#70 - 112
Get
Actual Sensor Reading
UDINT
Raw position value read from NR60E2
16#71 - 113
Get
Time Stamp
UDINT
Value increments every 400 nanoseconds.
Содержание NR60E2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual E2 Technology E2 Technology Manual 940 0D161...
Страница 6: ...TABLE OF CONTENTS NR60E2 User Manual ADVANCED MICRO CONTROLS INC 6 Notes...
Страница 20: ...NR60 SPECIFICATIONS NR60E2 User Manual ADVANCED MICRO CONTROLS INC 20 Notes...
Страница 44: ...PROTOCOL SPECIFIC INFORMATION NR60E2 User Manual ADVANCED MICRO CONTROLS INC 44 Notes...
Страница 52: ...IMPLICIT COMMUNICATIONS WITH AN EDS EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 52 Notes...
Страница 58: ...IMPLICIT COMMUNICATIONS WITHOUT EDS EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 58 Notes...
Страница 70: ...CIP POSITION SENSOR OBJECT EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 70 Notes...
Страница 90: ...PROFINET CYCLIC DATA FORMATS PROFINET Protocol ADVANCED MICRO CONTROLS INC 90 Notes...
Страница 98: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...