6.7 Troubleshooting
If you are unable to communicate with the NR60E2, the problem may be that the Ethernet port of your PLC
has not been configured. To check this on a MicroLogix 1100:
1) Double click on Channel Configuration in the Project Tree and then select the Channel 1 tab. The fol-
lowing window will open.
Figure R2.2 MicroLogix Ethernet Configuration Screen
2) Enter the IP address and Subnet Mask of your MicroLogix 1100, (not the address of the NR60E2)
and click on [Apply]. The Ethernet Port should now be working.
AMCI is aware of an issue with the RIX data type in version 10 of RSLogix 500. If you are
experiencing communications errors and are running version 10, please contact Rockwell
Automation for support.
Содержание NR60E2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual E2 Technology E2 Technology Manual 940 0D161...
Страница 6: ...TABLE OF CONTENTS NR60E2 User Manual ADVANCED MICRO CONTROLS INC 6 Notes...
Страница 20: ...NR60 SPECIFICATIONS NR60E2 User Manual ADVANCED MICRO CONTROLS INC 20 Notes...
Страница 44: ...PROTOCOL SPECIFIC INFORMATION NR60E2 User Manual ADVANCED MICRO CONTROLS INC 44 Notes...
Страница 52: ...IMPLICIT COMMUNICATIONS WITH AN EDS EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 52 Notes...
Страница 58: ...IMPLICIT COMMUNICATIONS WITHOUT EDS EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 58 Notes...
Страница 70: ...CIP POSITION SENSOR OBJECT EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 70 Notes...
Страница 90: ...PROFINET CYCLIC DATA FORMATS PROFINET Protocol ADVANCED MICRO CONTROLS INC 90 Notes...
Страница 98: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...