NX2A4E2 I
NTRODUCTION
NX2A4E2 User Manual
ADVANCED MICRO CONTROLS INC.
14
Status LED’s (continued)
Ethernet Status LEDs (continued)
Network Status (NS) LED
The Network Status LED is a bi-color red/green LED. The state of the LED depends on the protocol the
NX2A4E2 is configured to for.
Table R1.4 Network Status LED States
Link1 and Link2 LEDs
These are the Link Activity LEDs for the two ports. They are amber LEDs that are on when a valid hardware
connection exists on the port and blinking when data is being transferred over the link.
Input Status LEDs
These two red/green bi-color LED’s are used to indicate the on/off
status of the BRAKE and PRESET inputs. Note that the PRESET
function is not presently implemented. LED 2 will come on when
power is applied to the PRESET input, but the NX2A4E2 will not
change any position values. The BRAKE input is tied to channel 1.
When this input transitions from on to off, the unit starts a timer
and stops the timer when it does not detect a change in position on
channel 1 for 125 milliseconds. It then reports this time over the
network along with the channel 1 position when the input transi-
tioned. See
found on page 9, for a complete
description of how the brake input is used.
LED State
EtherNet/IP Definition
Modbus TCP Definition
PROFINET Definition
Off
No Power
No power or no TCP
connections
No power, duplicate IP
address on the network,
mismatch in Device Name,
or no connection to IO
Controller.
Alternating
Red/Green
Power up Self-Test
Power up Self-Test
Power up Self-Test
Blinking
Green
Ethernet connection, but
no CIP connections
Indicates number of connec-
tions with 2 second delay
between group. The
NX2A4E2 supports up to
five concurrent connections.
On-line, Stop state. A
connection with the IO
Controller is established and
it is in its STOP state.
Steady Green
Valid Ethernet network
and CIP connections
Not Implemented
On-line, Run state. A
connection with the IO
Controller is established and
it is in its RUN state.
Blinking Red
If the MS LED is steady
green: Network
Connection Timeout
Not Implemented
Not Implemented
If the MS LED is blinking green: IP Address or Network Protocol changed: Cycle
power
Steady Red
Duplicate IP address on network.
Not Implemented.
INPUT STATUS LED's
1: Brake Input
2: Preset Input (Not Implemented)
OFF: No Power Applied
RED: Power Applied, Pin 1/3 is
positive with respect to pin 2/4.
GREEN: Power Applied, Pin 2/4 is
positive with respect to pin 1/3.
1 2
Figure R1.4 Input Status LEDs
Содержание NEXUS NX2A4E2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0N090 E2 Technology...
Страница 16: ...NX2A4E2 INTRODUCTION NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 16 Notes...
Страница 28: ...DATA FORMATS NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 28 Notes...
Страница 52: ...PROTOCOL SPECIFIC INFORMATION NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 52 Notes...
Страница 56: ...INSTALLING AN EDS FILE EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 56 Notes...