INSTALLING THE ANR2
ADVANCED MICRO CONTROLS INC.
3
30
Extending the Transducer Cable (continued)
6-Wire Ratiometric
Figure 3.19 Extending a 6-Wire Ratiometric Sensor Cable
It is important to note the sense of the secondary windings and wire them appropriately. One
of the secondary windings must be in phase with the primary and one must be in anti-phase.
The sensor will not work if one of the secondary windings is reversed. The sensor will count
in the opposite direction if both of the phases are reversed.
Avoiding Ground Loops When Extending the Sensor Cable
A ground loop occurs when the shields of a cable are attached to earth ground in two places. It is possible,
and the likelihood increases as the cable length increases, for these two earth ground points to have a voltage
potential between them. The shield acts as a low impedance path between the two points which results in a
constant current flowing through the shield. To avoid a ground loop, the cable shields must not be grounded
in two places.
If the shield of the sensor cable is isolated from the body of the sensor, connect the shield of the sensor
cable to the shields of the Belden cable and ground the shield at the ANR2. Treat the shield of the sen-
sor cable as a signal carrying conductor and do not connect it to earth ground at any other point.
If the shield of the sensor cable is connected to the body of the sensor but the body of the sensor is iso-
lated from chassis ground by its mounting, connect the shield of the sensor cable to the shields of the
Belden cable and ground the shield at the ANR2. Treat the shield of the sensor cable as a signal carry-
ing conductor and do not connect it to earth ground at any other point.
If the shield of the sensor cable is connected to the body of the sensor and the body of the sensor is con-
nected to earth ground by its mounting,
Do Not
connect the shield of the sensor cable to the shields of
the Belden cable. The shield of the sensor cable is grounded by the sensor body. Connect the shields of
the Belden cable to earth ground at the ANR2.
B
A
B
+Exc
+Exc
Shields
–Exc
–Exc
GND
A
GND
GND
LVDT/RVDT
Sensor
RED
WHITE
BLACK
BLACK
BLACK
GREEN
Belden 9730 or equ.
NOTE:
Connection should only be
made if the sensor’s shield is isolated
from sensor body or sensor body is
not grounded. Connection must be
isolated from Earth Ground at this point.
Содержание ANR2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0A032...
Страница 14: ...INTRODUCTION TO THE ANR2 ADVANCED MICRO CONTROLS INC 1 14 Notes...
Страница 18: ...OPERATING MODES ADVANCED MICRO CONTROLS INC 2 18 Notes...
Страница 32: ...INSTALLING THE ANR2 ADVANCED MICRO CONTROLS INC 3 32 Notes...
Страница 36: ...AMCI NET CONFIGURATOR SOFTWARE ADVANCED MICRO CONTROLS INC 4 36 Notes...
Страница 48: ...CONFIGURATION MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 6 48 Notes...
Страница 58: ...ALIGNMENT MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 7 58 Notes...