INSTALLING THE ANR2
3
23
Sensor Wiring (continued)
4-Wire Sensor
There is only one way to wire a 4-wire sensor to an ANR2.
Figure 3.8 4-Wire LVDT/RVDT Wiring
5-Wire Sensor
Five wire sensors can be wired as either differential sensors or ratiometric sensors. Ratiometric wiring is less
sensitive to temperature variations, but the sensor must be manufactured for use as a ratiometric sensor. Con-
tact your sensor’s manufacturer if you are not sure which type of sensor you have.
Differential Wiring
Five wire sensors can be used as 4-wire sensors by leaving the centertap wire unconnected and electrically
isolated. As shown in the diagram below, you have the option of landing the centertap wire on one of the
N.C. pins of the ANR2 connector.
Figure 3.9 5-Wire LVDT/RVDT Differential Wiring
11
10
9
8
7
6
5
4
3
2
1
GND
N.C.
N.C.
B1
GND
GND
A1
–Exc
+Exc
Shield
SyncOut
ANR2 TOP VIEW
J1
J2
B
+Exc
–Exc
GND
GND
N.C.
N.C.
B2
GND
GND
A2
–Exc
+Exc
GND
SyncIn
11
10
9
8
7
6
5
4
3
2
1
Ch 1
Ch 2
NOTE:
This is a signal ground, not a shield ground.
All shields must be connected to J1-2 or the
earth ground connection of the ANR2 module.
NOTE:
Connection bExc output voltage and A input.
LVDT/RVDT
Sensor
NOTE:
Shields are typically grounded at the ANR2.
Verify that the shields are not connected to the sensor
body. If they are, and the body of the sensor is grounded,
do not attach the shields to the ANR2 if the sensor and
ANR2 do not
.
share a common ground
11
10
9
8
7
6
5
4
3
2
1
GND
N.C.
N.C.
B1
GND
GND
A1
–Exc
+Exc
Shield
SyncOut
ANR2 TOP VIEW
J1
J2
B
+Exc
–Exc
GND
N.C.
GND
N.C.
N.C.
B2
GND
GND
A2
–Exc
+Exc
GND
SyncIn
11
10
9
8
7
6
5
4
3
2
1
Ch 1
Ch 2
Connection bExc output voltage and A input must be made.
The sensor’s output centertap wire is not used and must remain electrically isolated. The wire can
be left unconnected or landed on pins J1-9 or J1-10.
This is a signal ground, not a shield ground. All shields must be connected to J1-2 or the earth
ground connection of the ANR2 module.
LVDT/RVDT
Sensor
Shields are typically grounded at the ANR2. Verify that the shields are not connected to the sensor
body. If they are, and the body of the sensor is grounded, do not attach the shields to the ANR2 if
the sensor and ANR2 do not
.
share a common ground
Содержание ANR2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0A032...
Страница 14: ...INTRODUCTION TO THE ANR2 ADVANCED MICRO CONTROLS INC 1 14 Notes...
Страница 18: ...OPERATING MODES ADVANCED MICRO CONTROLS INC 2 18 Notes...
Страница 32: ...INSTALLING THE ANR2 ADVANCED MICRO CONTROLS INC 3 32 Notes...
Страница 36: ...AMCI NET CONFIGURATOR SOFTWARE ADVANCED MICRO CONTROLS INC 4 36 Notes...
Страница 48: ...CONFIGURATION MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 6 48 Notes...
Страница 58: ...ALIGNMENT MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 7 58 Notes...