Страница 1: ...1002D amc VIBRO Sp z o o Pilotow 2e 31 462 Krakow Poland T 48 12 362 97 60 S 48 12 362 97 63 info amcvibro pl KRS No 0000618618 REGON No 364497010 VAT No 6772403385 www amcvibro pl VIBRATION MONITORIN...

Страница 2: ...etting up of the warning threshold U 8 7 4 Setting up of the threshold activation delay d 8 7 5 Setting up the latch of alarm or warning threshold violation L 8 7 6 Signaling of the sensor failure CA...

Страница 3: ...le warning and alarm relay outputs with the delay of the output build in connector for AC voltage signal from the vibration sensor 10 Vpp DIN rail mounting The AVM 1002D system is a perfect solution f...

Страница 4: ...nal 0 Peak Indicator of the selected measured value Green LEDs acc acceleration vel velocity Alarm outputs indicators Red LED ALARM the alarm threshold exceeded alarm output ON Yellow LED WARNING the...

Страница 5: ...5 AV MONITOR 1002D 3 Module dimensions 4 Mounting AVM 1002D module is designed for mounting on 35mm DIN rain in an upright position Figure 4 1 Example of 3 AVM 1002D modules mounted on DIN rail...

Страница 6: ...02D module enters into testing procedure Subsequently all display s segments and LEDs will flash for a short period of time If everything is operating properly then green OK LED is pulsing with a freq...

Страница 7: ...l estimate 7 2 Setting up of the alarm threshold A The AVM 1002D has the ability to activate the built in relay when the signal from the vibration sensor exceeds the threshold value To set the alarm t...

Страница 8: ...g the alarm threshold or the warning threshold should be exceeded before activating the relay output To set the delay one should perform the following procedure 1 Press UP DN Afterwards the OK LED wil...

Страница 9: ...P DN Afterwards the OK LED will blink rapidly which indicates entering into the device menu 2 By pressing UP DN set the CA on the display 3 Confirm by pressing the SET button 4 Use the UP DN buttons t...

Страница 10: ...are indicated by glowing decimal point on the right display 5 To confirm the change press the SET button 7 8 Turning display off on sensor failure Er The module enables to mask the incorrect measurem...

Страница 11: ...e following option PU 0 PEAK value of the velocity signal rU RMS value of the velocity signal PA 0 PEAK value of the acceleration signal rA RMS value of the acceleration signal 5 To confirm the change...

Страница 12: ...s filter for 100 mm s range and internal power loop The following configuration of the switches must be set SW1 OFF ON OFF OFF OFF ON OFF ON 1 8 SW2 OFF OFF OFF ON ON OFF 1 6 WARNING The set up of the...

Страница 13: ...13 AV MONITOR 1002D 9 Menu Graphical representation of menu structure is presented on the following figure...

Страница 14: ...nd 10 kHz 24 dB oct 4 th order high pass filter 3 and 10 Hz 12 dB oct 2 nd order insulation 1kV DC 2 or 3 kV DC optionally current output 2 or 3 wired 4 20 mA current loop voltage output AC 10Vpp max...