If the vibration sensor signal will exceed the alarm threshold value and will remain above it for the time 
the configured delay, the alarm relay will be activated. 

 

To disable the alarm threshold, instead of the numerical value from the range from 0.0 to 99, set the 
FF’ value on the display and confirm by pressing the SET button. 

 

7.3

 

Setting up of the warning threshold ‘U’ 

 

The second relay installed in the AVM 1002DX module is marked WARNING. It informs about 
excitation of the warning level of the signal. 

 

To set the warning threshold one should perform the following procedure: 

 

1.

 

Press 

UP/DN

. Afterwards the 

OK

 LED will blink rapidly, which indicates entering into the 

device menu. 

 

2.

 

By pressing 

UP

/

DN

 set the letter ‘

U

’ on the display. 

 

3.

 

Confirm by pressing the 

SET

 button. 

 

4.

 

Use the 

UP

/

DN

 buttons to select the desired warning threshold value in the range from 

0.0

 

to 

99

. Warning threshold value cannot be greater than the alarm threshold value. 

 

5.

 

To confirm the change, press the 

SET

 button. 

 

To disable the warning threshold, instead of the numerical value from the range from 

0.0

 to 

99

, set the 

FF

 value on the display and confirm by pressing the 

SET

 button. 

 

7.4

 

Setting up of the threshold activation delay ‘d’ 

 

In the AVM 1002DX module the user can define how long the alarm threshold or the warning 
threshold should be exceeded before activating the relay output. 

 

To set the delay one should perform the following procedure: 

 

1.

 

Press 

UP/DN

. Afterwards the 

OK

 LED will blink rapidly, which indicates entering into the 

device menu. 

 

2.

 

By pressing 

UP

/

DN

 set the letter ‘

d

’ on the display. 

 

3.

 

Confirm by pressing the 

SET

 button. 

 

4.

 

Use the 

UP

/

DN

 buttons to select the desired delay time in the range from 

0

 to 

16

 s. 

 

5.

 

To confirm the change, press the 

SET

 button. 

 

7.5

 

Setting up the latch of alarm or warning threshold violation ‘L’ 

 

AVM 1002DX has the ability to store the information about the violation of the warning or the alarm 
threshold. When the violation occurs, after the delay ‘

d

’, proper relay is activated until the user erases 

the violation information by pressing the 

SET

 button. 

 

To set up the latch one should perform the following procedure: 

 

1.

 

Press 

UP/DN

. Afterwards the 

OK

 LED will blink rapidly, which indicates entering into the 

device menu. 

 

2.

 

By pressing 

UP

/

DN

 set the letter ‘

L

’ on the display. 

 

3.

 

Confirm by pressing the 

SET

 button. 

 

4.

 

Use the 

UP

/

DN

 buttons to select the 

ON

 option. 

 

5.

 

To confirm the change, press the 

SET

 button. 

 
 
 
 
 
 

8

 

AV MONITOR 1002DX 

Содержание AV MONITOR 1002DX

Страница 1: ...2 Krakow Poland T 48 12 362 97 60 S 48 12 362 97 63 info amcvibro com KRS No 0000618618 REGON No 364497010 VAT No 6772403385 www amcvibro com AV MONITOR 1002DX CONDITION MONITORING SYSTEM WITH RELAY O...

Страница 2: ...the threshold activation delay d 8 7 5 Setting up the latch of alarm or warning threshold violation L 8 7 6 Signaling of the sensor failure CA CU 9 7 7 Setting up the correction of values indicated by...

Страница 3: ...urement calculation of RMS or 0 PEAK values configurable warning and alarm relay outputs with the delay of the output build in connector for AC voltage signal from the x vibration sensor 10 Vpp DIN ra...

Страница 4: ...Peak Indicator of the selected measured value Green LEDs acc acceleration vel velocity Alarm outputs indicators Red LED ALARM the alarm threshold exceeded alarm output ON Yellow LED WARNING the warnin...

Страница 5: ...3 Module dimensions 4 Mounting AVM 1002DX modules are designed for mounting on 35 mm DIN rain in an upright position Figure 4 1 Example of 3 AVM 1002DX modules mounted on DIN rail 5 AV MONITOR 1002DX...

Страница 6: ...into testing procedure Subsequently all display s segments and LEDs will flash for a short period of time If everything is operating properly then green OK LED is pulsing with a frequency of approxima...

Страница 7: ...values indicated by the module Er turning display off on sensor failure AU selection of vibration signal estimate ATTENTION In some types of AVM 1002DX modules some of the above functions are not act...

Страница 8: ...confirm by pressing the SET button 7 4 Setting up of the threshold activation delay d In the AVM 1002DX module the user can define how long the alarm threshold or the warning threshold should be exce...

Страница 9: ...OK LED will blink rapidly which indicates entering into the device menu 2 By pressing UP DN set the CA on the display 3 Confirm by pressing the SET button 4 Use the UP DN buttons to select the ON opt...

Страница 10: ...decimal point on the right display 5 To confirm the change press the SET button 7 8 Turning display off on sensor failure Er The AVM 1002DX module enables to mask the incorrect measurement values in t...

Страница 11: ...T button 7 10 Relay output state configuration uA uU The AVM 1002DF has a special feature to control relay output state normally open or normally closed The configuration can be done independently for...

Страница 12: ...is set by proper set up of configuration switches SW1 and SW2 Description of switches SW1 and SW2 is presented in the following table and Figure 8 1 Functions of configuration switches SW 1 SW2 S1 ON...

Страница 13: ...d internal power loop The following configuration of the switches must be set SW1 SW2 OFF ON OFF OFF OFF ON OFF ON OFF OFF OFF ON ON OFF 1 8 1 6 WARNING The set up of the switches configuration should...

Страница 14: ...9 Menu Graphical representation of menu structure is presented on the following figure 14 AV MONITOR 1002DX...

Страница 15: ...n 4 W low pass filter DX 1 and 10 kHz 24 dB oct 4 th order DT no LPF filter high pass filter DX 3 and 10 Hz 12 dB oct 2 nd order DT no HPF filter insulation 1 kV DC 2 or 3 kV DC optionally current out...

Страница 16: ...ent chromium polybrominated biphenyls polybrominated diphenyl ether or other battery related materials are limited to no more than trace amounts 10 2 Recycling Facilities When decommissioning out of u...

Отзывы: