OPERATION INSTRUCTIONS
Leak Check
WARNING
• Perform all leak tests outdoors.
• Extinguish all open flames.
• NEVER smoke while carrying out the leak test.
• Do not use the fire feature until all connections have
been leak tested and do not leak.
Hose / Regulator
connection
Regulator / Cylinder
connection
1. Make 6-8 oz. of leak check solution (one part liquid dish washing detergent and three parts water).
2. Make sure tank valve is OFF and valve to Ambiance Fire Feature is in OFF Position
3. Apply several ounces of solution where hose attaches to regulator.
4. Apply several ounces of solution where regulator connects to cylinder; apply the soapy solution
to all hose & valve connections.
5. Turn tank cylinder valve ON.
If bubbles appear at any connection, there is a leak, follow instructions below:
1. Turn cylinder valve OFF.
2. If leak is at hose/regulator connection: Tighten accordingly with wrenches. The fittings are flare
to flare and tape of sealant should not be used. If bubbles continue appearing, the hose should be
returned to the place of purchase or contact AEI Corporation at (949) 474-3070.
3. If leak is at regulator/cylinder valve connection: disconnect, reconnect, and perform another leak
check. Apply the soapy solution to all hose & valve connections. If you continue to see bubbles
after several attempts, cylinder valve or regulator fitting is defective and should be returned to
cylinder’s place of purchase.
If NO bubbles appear at any connection, the connections are secure.
NOTE: Whenever gas connections are loosened or removed, you must perform a complete
leak test.