background image

Description

Control board installation procedures are described in detail
in these instructions. Read and follow these instructions
carefully before replacing the control board. Failure to do so
may result in control board damage.

Important Note:

Damage to the control board can occur from failure to
disconnect power supply or failure to set the master switch
(located on the control board) to OFF before removing the
low voltage terminal strip cover from an installed control
board. Damage to this board by not following these instruc-
tions is considered misuse and not covered under either the
standard unit warranty or any extended service contract.

Important Note:

All warranty replaced boards must be returned to the parts
source from which they were purchased to insure proper
warranty credit.

PTAC CONTROL BOARD KIT

RSKP0006

I

NSTALLATION

  I

NSTRUCTIONS

IO-660A
November 2006

ATTENTION INSTALLING PERSONNEL

As a professional installer you have an obligation to know the product better than the customer.  This

includes all safety precautions and related items.

Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention
to all safety warnings. Often during installation or repair it is possible to place yourself in a position which is

more hazardous than when the unit is in operation.

Remember, it is 

your 

responsibility to install the product safely and to know it well enough to be able to

instruct a customer in its safe use.

Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific

good safety practices...follow them.

The precautions listed in this Installation Manual are intended as supplemental to existing practices.

However, if there is a direct conflict between existing practices and the content of this manual, the

precautions listed here take precedence.

RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.

Figure 1

Electrostatic Discharge (ESD) Precautions

Before removing the new control board from the static wrap,
it is very important to discharge any static electricity. This
can be accomplished in two methods.  Servicer can wear a
ground strap or by touching the metal chassis before replac-
ing the board.

Existing Control Board Removal Procedures

1. Disconnect power to the unit by unplugging the power

cord at the wall outlet or subbase, or disconnect power at
the fuse box or circuit breaker.

2. If the cabinet front is screwed to the chassis, remove the

1/4” screw (or screws) located behind the inlet grille.  Pull
the inlet grille forward from the top of the grille to access
screw(s).

FRONT MOUNTING

HOLE

Printed in USA

Содержание RSKP0006

Страница 1: ...or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of specific good safety practices follow them T...

Страница 2: ...ges Orient the control panel so there is easy access for mounting components to the inside of the control panel 11 Using the two 8 screws that are provided screw the transformer that was provided with the kit to the control panel in the transformer mounting holes provided in the panel See Figure 3 12 The external transformer will come with the Black 37 wiresconnectedtotheLOADterminalofthetransform...

Страница 3: ...lluminated continu ously For status light functionality the YELLOW thermistor MUST be installed Instructions are as follows A1 Carefully cut and remove the gasket on the left and right sides of discharge screen Remove the two 2 5 16 screwsholdingtheindoorexhaustscreenabove the indoor coil Remove the indoor exhaust screen Removethetwo 2 1 4 screwsconnectingtheheater panel to the evaporator coil Rem...

Страница 4: ...sed on the bent coil and an additional clip loose in the bag will fit 3 8 tubing used on the flat slab coil Ifyouhaveaslabcoil youwillneedtoremovethe5 16 clip from the sensor and replace it with the 3 8 tube clip ConnecttheOutdoorCoilThermistortotheboard as noted above Outdoor Coil Thermistors are only usedonHeatPumpmodels DONOTINSTALLTHIS SENSOR IF THE UNIT IS NOT A HEAT PUMP Figure 7 INDOOR COIL...

Страница 5: ...in connector to low voltageterminalstrip If replacing a previous version board you will need to use the 18 pin connector supplied with the board for low voltage accessories Wires supplied with this kit have terminal ends on the wires Insert the terminal end into the correctly labeled slot push in and it will lock in place After loading pin connector use the wire nuts supplied with the kit to wire ...

Страница 6: ...6 BLACK w WHITE STRIPE YELLOW w BLACK STRIPE RED GREEN WHITE YELLOW BLUE GREEN w YELLOW STRIPE Remote Thermostat BROWN Only load wires needed for accessories attached to unit Figure 9 ...

Страница 7: ...E FAN LOW FAN HIGH LINE 1 ON 24VAC TRANSFORMER DSI IN GL GH B YELLOW Heat Pump models ONLY Must not be used on PTC models RIBBON CONNECTOR Left is ON Position YELLOW ORANGE from Touch Pad BLUE RED BLACK Figure 10 ...

Страница 8: ...TAGE FOR A HEAT PUMP OFF 2 RIBBED WIRE MUST BE CONNECTED AS SHOWN ANTICIPATOR GN 1 R TO HEAT PUMP W AUXILIARY REMOTE THERMOSTAT OPERATION FAN PANEL W ELECTRIC HEAT CHASSIS R TO 2ND STAGE 1ST STAGE G Y W1 FACTORY OR FIELD FACTORY OR FIELD HEAT OFF 230 265 COM TRANSFORMER LOAD SOLENOID R SWITCH BK18 YL10 BR14 ELECTRIC GY22 C CAP H HEATER 4 1 DESK 2 F 19 WIRE RD17 RD13 BK16 S OD VALVE C G N RIBBED FA...

Страница 9: ...ITCH ON OFF VT12 5 BK18 MO OR T 1 LINE CO M 208 240 FAN MUFFIN 20 HEATER ELECTRIC CAP FAN COMP OD WH15 BR14 19 SOLENOID VALVE 2 GN WIRE RIBBED H C F YL10 RD13 S C R R TO G Y W1 G B Y W1 G W2 FUNCTION OFF 1ST STAGE HEAT 2ND STAGE HEAT R TO G Y W1 FUNCTION OFF HEAT G FAN G FAN FOR A HEAT PUMP THERMOSTAT USED ON A STRAIGHT COOL UNIT GL low speed GH high speed W ELECTRIC HEAT COOLING UNIT ELECTRIC HEA...

Страница 10: ... AND 115V TRANSFORMER NOT SHOWN 240 208 COM LINE OR8 CP 7 FOR REMOTE OPERATION SEE CONFIGURATION CHART 6 YL1 CP YL5 CP YL3 CP BK16 RD17 WH 6 CP HEAT PUMP W AUXILIARY ELECTRIC HEAT R TO G Y W1 G B Y W1 G W2 FUNCTION OFF COOL 1ST STAGE HEAT 2ND STAGE HEAT COOLING UNIT W ELECTRIC HEAT CONNECT R TO G Y W1 FUNCTION OFF REMOTE THERMOSTAT OPERATION HEAT G FAN G FAN FOR A HEAT PUMP THERMOSTAT USED ON A ST...

Страница 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK ...

Страница 12: ... product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Better Quality Visit our website at www amana ptac com for information on Products Warranties Customer Services Parts Contractor Programs and Training Financing Options 2006 Goodman Company L P is a ...

Отзывы: