5.43
Instrument address for optional serial communications
Display:
Addr
Range:
0
to
31
Default Value:
0
Set unit address for polled (
POLL
) or
M.buS
mode (
0
to
31
)) - seen only with serial output option.
Refer to the separate “RM4 Din Rail Meter Optional Output Addendum” booklet supplied when
optional outputs are fitted. Allows several units to operate on the same RS485 interface reporting
on different areas etc.
The host computer or PLC may poll each unit in turn supplying the
appropriate address. The unit address ranges from 0 to 31 (DEC) but is offset by 32 (DEC) to
avoid clashing with ASCII special function characters (such as
<
STX
>
and
<
CR
>
). Therefore 32
(DEC) or 20 (HEX) is address 0, 42 (DEC) or 2A (HEX) is address 10. Do not use address 0 in
M.buS
mode.
5.44
Serial mode for optional serial communications
Display:
SERL
Range:
LiuE, tARE, P.HLd, d.HLd, Hi, Lo, HiLo
or
dISP
Default Value:
LiuE
Seen only with serial output option - applies only when
O.Put
function set to
Cont
. Refer to
rEC
function. The
HiLo
selection in this functions allows both the peak and valley memories to
be transmitted. The peak value will be transmitted followed by a space then the valley value.
5.45
Error Messages
“
- - - -
” - This display indicates that the input signal is higher than the maximum rated input.
Check the input links to ensure that the correct range is selected and then if necessary check the
input voltage.
“
-or-
” - This display indicates an overrange reading. This means that the instrument is not able
to display the number because it is too large to fit on to the display e.g. above 99999. Check that
the calibration scaling figures are correct. Alternatively this message can be seen if either the
Lo
dISP
or
HIGH dISP
values have been exceeded and the
dISP
function is set to
-or-
.
SPANErr
- this message indicated that the input was not changed by a sufficient percentage
during calibration - see “Calibration” chapter.