5.22
Decimal point
Display:
dCPt
Range:
0
,
0.1
etc.
Default Value:
0
Displays and sets the decimal point. By pressing the
^
or
v
pushbutton at the
dCPt
function
the decimal point position may be set. The display will indicate as follows:
0
(no decimal point),
0.1
(1 decimal place),
0.02
(2 decimal places),
0.003
(3 decimal places) and
0.0004
for display
with more than 4 digits. Note if the decimal point is altered the display will need to be recalibrated
and alarm etc. settings checked.
5.23
Digital filter
Display:
FLtr
Range:
0
to
8
Default Value:
2
Displays and sets the digital filter value.
Digital filtering uses a weighted average method of
determining the display value and is used for reducing display value variation due to short term
interference. The digital filter range is selectable from
0
to
8
, where
0
= none and
8
= most
filtering. Use
^
or
v
at the
FLtr
function to alter the filter level if required. Note that the
higher the filter setting the longer the display may take to reach its final value when the input is
changed, similarly the relay operation and any output options will be slowed down when the filter
setting is increased. To set the digital filter value go to the
FLtr
function and use the
^
or
v
push buttons to set the required value then press
F
to accept this selection.
5.24
P
button function
Display:
P.but
Range:
NONE, Hi, Lo, HILo, ZERO
or
P.SEt
Default Value:
NONE
P
button function - The
P
button (5, 6 or 8 digit LED models only) may be set to operate
some of the remote input functions. With the
P.SEt
and
ZERO
functions, to prevent accidental
operation, the
P
button must be held pressed for 2-3 seconds before the display will go to the
preset value or zero. The
P.SEt
and
ZERO
functions operations will only work if either the
U.SCL
or
USER SCLE
function is set to
on
. If both the remote input and
P
button function
are operated simultaneously the
P
button will override the remote input. The functions below are
as described in the
R.INP
function below.
22 of
PM4SSIMAN-2.2-0