5.79
Channel display filter
Section:
CH 1
to
CH 8
Display:
FLtR
Range:
0
,
1
,
2
,
3
,
4
,
5
,
6
,
7
,
8
Default Value:
0
Default Access Level
CAL
Function number
43C0
to
43C7
Seen when the
CONF CodE
function is set to
SCAN
. Displays and sets the digital filter value for the selected
channel. Digital filtering uses a weighted average method of determining the display value and is used for reducing
display value variation due to short term interference. The digital filter range is selectable from
0
to
8
, where
0
=
none and
8
= most filtering.
5.80
Channel display polarity
Section:
CH 1
to
CH 8
Display:
Ch.PL
Range:
both
,
PoS
,
NEg
,
AbS
Default Value:
both
Default Access Level
CAL
Function number
4dA0
to
4dA7
Seen when the
CONF CodE
function is set to
SCAN
. Displays and sets the polarity selection for the display for
the selected for channel. If set to
both
then both positive and negative values can be displayed. If set to
PoS
the
display will allow only positive values with any values below zero being rounded to zero. If set to
NEg
then the
display will allow only negative values with any value above zero being rounded to zero. If set to
AbS
then both
positive and negative values received will be displayed as positive values.
5.81
Channel display on or off
Section:
CH 1
to
CH 8
Display:
dISP
Range:
OFF
or
ON
Default Value:
On
Default Access Level
4
Function number
44F0
to
44F7
Allows selection of which channels will be seen and which not seen on the display. If set to
OFF
that selected
channel will not be seen on the display. If set to
ON
that channel will be seen on the display. For example when
adding two channels together using a calculated channel it may be required that channel 1 and channel 2 not be seen
on the display so that only the sum (produced by the calculated channel) is seen.
5.82
Calculation channel function
Section:
CC 1
to
CC 8
Display:
Func
Range:
Hi
,
Lo
,
dIFF
,
AUg
,
d.AUg
,
P.AUg
,
N.AUg
,
S.dIF
,
Add
,
PC 1
,
PC 2
,
Sub
,
Prod
,
diu
,
SinE
,
CoS
,
R.AUg
,
F.AUg
Default Value:
Hi
Default Access Level
4
Function number
4E10
to
4E17
Allows selection of the function to be used for each calculated channel. Options are:
LD5RSMAN-2.0-0
55 of